3
3.3
Parameterizing using the parameterizing and start–up tool SimoCom U
3-102
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 3-3
Information on SimoCom U, continued
Function
Description
Commissioning
required
A drive that has still not been commissioned, logs–on with:
”Commissioning required!”
You have 5 possibilities:
1. Open the Start–up Assistant – if you have not already created a file, which
you wish to load into the drive.
2. Load an existing file into the drive.
3. Optionally, you can switch the drive, which logs–on, into the passive state
(this is only possible for drive B).
4. Work offline – this means that you disconnect the link to the drive without
start up the drive.
5. Emergency exit – in this case, you remain online without carrying out any
commissioning (e.g. in order to upgrade the firmware before commissioning)
Procedure when
commissioning
Recommendation:
Go through the ”Start–up” menu, from the top to the bottom.
The parameters are arranged according to importance:
1.)
Drive configuration
... here, enter which power modules, which motors, which encoders are used
with this drive, and in which operating mode the drive is used.
If this data is changed, the controller data is re–calculated,
i.e. previous changes made to the relevant parameters will be overwritten.
2.)
Basic commissioning
... here, you will find the data, which is in most cases necessary and also
sufficient for the motor and the operating mode that has been entered.
You can access all of the parameters in the expert list.
Traverse the drive
After the drive has been configured, you can already operate the drive from the
PC.
Call: ”Operator control/Traverse/ ...” menu
Data transfer
Also here, the program attempts to ”think with you”:
If you are working with drive A and select ”File/Load into drive”, then the
program assumes that you wish to download a file, still to be selected, into this
drive A.
If a file is presently open, then the program assumes that using the same
command, you wish to download this open data set into a drive still to be
selected.
If these assumptions are not applicable, then you can always undo by
canceling.
3 Parameterizing the Board