3
3.3
Parameterizing using the parameterizing and start–up tool SimoCom U
3-105
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The serial RS232 interface is used to connect the ”SIMODRIVE 611
universal” control board to a PG/PC.
The parameterizing and start–up tool SimoCom U communicates via
this interface in the online mode (refer to Fig. 3-9).
Note
When changing the drive (changing–over the serial connecting cable)
while there is an open connection to SimoCom U, first wait until the
SimoCom U has recognized that the connection has been interrupted
(a dialog box opens within a few seconds). You can then insert the
cable into the new drive. In the dialog box, you can then select whether
you wish to re–connect or cancel.
The following should be observed when establishing a communications
link:
1. Parameter P0801 ”toggling between RS232/RS485)”:
The parameter must be set to RS485 (P0801 = 0).
Recommendation:
Set or check this parameter using the display and operator panel
(refer to Chapter 3.2).
2. RS232 connecting cable
between PG/PC and ”SIMODRIVE 611 universal”
(cable diagram: refer to Chapter 2.5).
Serial interface (X471)
RS232 connecting cable
SIMODRIVE 611 universal
Serial
interface (e.g.
COM 1)
Parameterizing
and start–up tool
”SimoCom U”
PG/PC
Setup.exe
Fig. 3-9
Communications via RS232
Communications
via RS232
3 Parameterizing the Board
01.99
! 611ue diff !
02.02