A.1
Parameter list
A-777
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0878
PROFIdrive configuration
(–> 8.2)
Min
Standard
Max
Unit
Data type
Effective
0
0
7
Hex
Unsigned16
immed.
... several behavioral features are activated in order to achieve conformance with the PROFI-
drive profile.
Bit 0
Axis addressing according to PROFIdrive
Bit 0 = 0
For a non-cyclic access via the DPV1 parameter channel axis A is addressed
with index 1 (this is in conformance with the profile)
Bit 0 = 0
For a non-cyclic access via the DPV1 parameter channel axis A is addressed
with index 0 (this is not in conformance with the profile)
Bit 1
P915/P916 cannot be changed for P922 > 0
Bit 1 = 0
P915/P916 cannot be written into if P922 is greater than 0 (this is in conformance
with the profile)
Bit 1 = 0
P915/P916 can also be written into if P922 is greater than 0 (this is not in
conformance with the profile)
Bit 2
No. of Value = Length for string variables
Bit 2 = 1
For string variables, in the ”DPV1 parameter response” the length of bytes is
transferred under ”No. of Values” (in conformance with the profile)
Bit 2 = 0
For string variables, in the ”DPV1 parameter response” the number of values are
transferred under ”No. of Values” (this is not in conformance with the profile)
Note:
The following parameters should be set to ensure conformance with the PROFIdrive profile:
P878 Bit 0 = 1, Bit 1 = 1, Bit 2 = 1
P879 Bit 0 = 1, Bit 1 = 0, Bit 2 = 0, Bit 9 = 1
P1012 Bit 12 = 1, Bit 13 = 1, Bit 14 = 0
A Lists
01.99
! 611ue diff !
04.05