SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0916:17 PZD actual value assignment PROFIBUS
(–> 3.1)
Min
Standard
Max
Unit
Data type
Effective
0
0
65535
–
Unsigned16
immed.
... serves for allocating the signals to the process data in the actual value frame.
The following applies:
P0916:0
no meaning
P0916:1
PZD1, unable to configure (standard setting)
P0916:2
PZD2, Configuring and display of the signal ID (refer to P0922)
P0916:3
PZD3, etc.
ID
Significance (abbreviation) (comments)
0
No signal (NIL)
50002
Status word 1 (ZSW1) (assignment, n-set operation)
50002
Status word 1 (ZSW1) (assignment pos operation)
50004
Status word 2 (ZSW2)
50006
Speed actual value A (NACT_A, nact-h)
50008
Speed actual value B (NACT_B, nact-(h+l))
50010
Encoder 1 status word (G1_ZSW) (n-set operation)
50011
Encoder 1 position actual value 1 (G1_XACT1) (n-set operation)
50012
Encoder 1 position actual value 2 (G1_XACT2) (n-set operation)
50014
Encoder 2 status word (G2_ZSW) (n-set operation, from SW 3.3)
50015
Encoder 2 position actual value 1 (G2_XACT1) (n-set operation, from SW 3.3)
50016
Encoder 2 position actual value 2 (G2_XACT2) (n-set operation, from SW 3.3)
50018
Encoder 3 status word (G3_ZSW) (n-set operation)
50019
Encoder 3 position actual value 1 (G3_XACT1) (n-set operation)
50020
Encoder 3 position actual value 2 (G3_XACT2) (n-set operation)
50102
Message word (MeldW)
50104
Analog input T. 56.x/14 (ADU1)
50106
Analog input T. 24.x/20 (ADU2)
50108
Digital inputs, T. I0.x to I3.x (DIG_IN)
50110
Utilization (util)
50112
Active power (Pactive)
50114
Smoothed torque setpoint (Mset)
50116
Smoothed torque-generating current Iq (IqGl)
50118
Status word, slave-to-slave communications (QZsw) (pos operation,
from SW 4.1)
50119
DC link voltage (VDClink1) (from SW 8.3)
50202
Currently selected block (AktSatz)
50204
Positioning status word (PosZsw) (pos operation)
50206
Position actual value (positioning operation) (XistP) (pos operation)
50208
Position reference value (positioning operation) (XsollP) (pos operation,
from SW 4.1)
50210
Correction position reference value (Xcor) (pos opertion, from SW 4.1)
Note:
If this parameter is read via non-cyclic communication (PROFIdrive), then the indices have
been shifted. Index 1 corresponds to Index 0 (etc.) in the description of the PROFIdrive profile.
Operating mode not specified ––> possible in every operating mode
refer to the index entry ”Configuring the process data”