IM05805004K
Effective January 2003
Instructions for Cutler-Hammer
Jockey Pump Controllers
Page 1: ...IM05805004K Effective January 2003 Instructions for Cutler Hammer Jockey Pump Controllers IM05805004K...
Page 2: ......
Page 3: ...1 ELECTRICAL CHECKOUT INSTRUCTIONS 2 3 1 1 Motor Rotation Check 2 3 1 2 Pressure Switch Set Point 2 3 1 3 Starting and Stopping 2 3 1 4 Overload Relay Trip Setting 2 3 1 5 Running Period Timer Optiona...
Page 4: ......
Page 5: ...bottom external side of the enclosure The connection should be installed as per NFPA pamphlet No 20 NOTE Water lines to the pressure switch must be free from dirt and contamination The pressure should...
Page 6: ...structions These instructions check out automatic starting and stopping 3 1 3 Starting and Stopping Energize the controller With the H O A selector switch set to AUTO if the system water pressure is l...
Page 7: ...pump starting pressure Turn the Range Adjusting Screw clockwise to reduce the pressure and observe the scale on the switch 2 Bleed the fire protection water system until the pressure is reduced to the...
Page 8: ...IM05805004K Effective January 2003 Page 4 FIGURE 1...
Page 9: ...IM05805004K Effective January 2003 FIGURE 2 Page 5...
Page 10: ...IM05805004K Effective January 2003 FIGURE 3 Page 6...
Page 11: ...IM05805004K Effective January 2003 Page 7...
Page 12: ...er Hammer 403 East Lake Blvd Airdrie Alberta T4A 2G1 Canada tel 403 948 7955 fax 403 948 6967 www chfire com 2003 Eaton Corporation All Rights Reserved Printed in Canada Publication No IM05805004K Jan...