COM600 series 5.1

Operator's Manual

Summary of Contents for COM600 series

Page 1: ...COM600 series 5 1 Operator s Manual...

Page 2: ......

Page 3: ...ccess permissions 12 3 3 2 Adding new users 14 3 3 3 Modifying user properties 14 3 3 4 Changing user s password 15 3 3 5 Changing user language 15 3 4 Connecting WebHMI to the COM600 computer 15 3 5...

Page 4: ...3 Filtering events 35 3 9 Data Historian 36 3 10 Disturbance data upload 37 3 10 1 Disturbance recordings 37 3 11 Parameter setting 39 3 11 1 Changing parameters 39 3 12 Measurements 42 3 12 1 Viewing...

Page 5: ...ath shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risk...

Page 6: ...rs General information 1 5 This manual provides information on GridAutomation Controller COM600 later referred to as COM600 Web Human Machine Interface WebHMI Information in this manual is intended fo...

Page 7: ...icons that point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The corresponding icons should be interpreted as...

Page 8: ...physical IEC 61850 device that behaves as its own commu nication node in the IEC 61850 protocol Intelligent Electronic Device Series of standards specifications aiming at open connectivity in industr...

Page 9: ...anual 1MRS756567 DNP 3 0 Serial Master OPC User s Manual 1MRS755495 DNP 3 0 Serial Slave OPC User s Manual 1MRS755382 IEC 60870 5 101 Slave OPC User s Manual 1MRS756703 IEC 60870 5 101 Master OPC User...

Page 10: ...e 2 2 To facilitate substation and grid automation solutions in IEC and ANSI market areas a variant based system similar to Relion 615 and 620 series is being followed from COM600 5 0 release The main...

Page 11: ...different users in a professional and user friendly manner The web technology is further used to transfer information to a network control centre NCC or distributed control system DCS COM600 benefits...

Page 12: ...the Single Line Diagram view Events Shows the events list Alarms Shows the alarms list Data historian Shows the data historian information Optional feature Help Shows the WebHMI help Logout Predefined...

Page 13: ...ss permissions using local browser If enabled in COM600 local browser only administrator users are allowed to resize the WebHMI window access COM600 files launch and switch to other application access...

Page 14: ...Type in a new user name The length of the user name can be 1 99 characters and it can only contain characters a z and 0 9 4 Type in a password and confirm it The length of the password can be 9 99 cha...

Page 15: ...anguage settings 1 Click the User or Settings tab on the left 2 Click Change Language 3 Select User Interface Language to use 4 Select Culture to use determines date and time formats 5 Click Apply Can...

Page 16: ...functions You can see the status of the IEDs in the substation structure If there is a problem in communication there is a red cross next to the IED Document_Library png Figure 3 5 1 1 The substation...

Page 17: ...cument library Documents that are added to the document library and referenced to substation objects in the configuration phase can be accessed from the sustation tree view Document links are shown ei...

Page 18: ...1 The communication view to WebHMI Device and diagnostics information 3 5 3 By clicking the computer name at the top of the structure the system information such as the hardware and software versions...

Page 19: ...communication status or diagnostic counter information of individual devices click the IED objects Single Line Diagram 3 6 General information about Single Line Diagram 3 6 1 A Single Line Diagram SLD...

Page 20: ...Substation View has been defined it will be displayed Otherwise the Master View will be shown Voltage level and bay SLD can be opened in the substation tree by clicking their names in the tree V1 H1...

Page 21: ...Select the control direction by clicking Open or Close 2 Click Operate to activate the selection or Cancel to cancel the operation Some of the buttons can be disabled depending on the state of the sw...

Page 22: ...corresponding interlock or syncrocheck test Overriding of interlock and synchrocheck tests can be danger ous Only use the override option if you are sure that the operation can be performed safely wi...

Page 23: ...ate 3_state_switch_control_open bmp Figure 3 6 3 2 The Three state switch control dialog for Open state Operator place 3 6 4 The operator place setting is common to all SLD control dialogs and lets th...

Page 24: ...he device is blocked from open and close control from remote or local WebHMI If Hot Line Tag is applied to Tap changer raising and lowering and operation modes are dis abled To apply Hot Line Tag 1 Op...

Page 25: ...emote local WebHMI or SCADA system 7 Click Apply to apply Hot Line Tag Hot_Line_Tag bmp Figure 3 6 5 1 1 Applying the Hot Line Tag To remove the Hot Line Tag 1 Open Switch Device Control Dialog by cli...

Page 26: ...caption into the Caption text box 4 Enter a description of the Information Tag 5 Click Apply to apply the Information Tag Information_Tag bmp Figure 3 6 5 2 1 Applying the Information Tag To remove th...

Page 27: ...n by entering a numeric value You must have the required user permissions to perform these changes and local remote switch must allow the operation The tap changer must also be in manual operating mod...

Page 28: ...control based on the current status of the device The capacitor symbol should be connected to an appropriate ZCAP logical node during the SLD configuration The ZCAP logical node offers two data objec...

Page 29: ...Information Tag can also be applied to the Tap Changer mode For detailed information see 3 6 5 1 Hot Line Tag and 3 6 5 2 Information Tag Capacitor_Bank_Control png Figure 3 6 7 1 Capacitor Bank Contr...

Page 30: ...cted from the drop down menu on the top of the Single Line Diagram View There are four modes of busbar coloring 1 No busbar coloring All sections are displayed in a default color 2 Powered Unpowered b...

Page 31: ...line which describes the cause of the alarm in the process The alarm text line includes date time bay device object text state status and quality The blinking symbol in the upper right corner of WebHM...

Page 32: ...egistered and identified the alarm Acknowledging an alarm does not remove the alarm but changes the alarm state An acknowledged alarm is displayed in blue in the Persisting alarms list Inactive alarms...

Page 33: ...rm footer 3 7 5 The alarm footer appears at the bottom of the WebHMI It shows three alarm rows and you can scroll it to view all alarms The alarms are color coded Red active alarms Black inactive alar...

Page 34: ...logging in and so on The Events list includes the following information date time bay device object text event and quality For quality flag information and explanations of the flag meaning see Append...

Page 35: ...st is saved in csv format and can be opened in MS Excel change the number of alarms displayed on the list by selecting the number from the drop down list change the order in which the events are displ...

Page 36: ...nsive history recording The data historian is based on ABB s cpmPlus Knowledge Manager software It combines the benefits of an easy to use real time database with industrial reliability performance an...

Page 37: ...10 Disturbance recordings 3 10 1 Most of the IEDs are equipped with a Disturbance recording function that locally stores the values of currents voltages frequencies and binary signals in a disturbance...

Page 38: ...te disturbance recordings from the COM600 computer select the check box of the corresponding recording and click Delete The Select All button inverts the current selection as follows If no recordings...

Page 39: ...10 1 2 Wavewin disturbance record display and analysis software Parameter setting 3 11 Changing parameters 3 11 1 You can view parameter information by clicking on Parameters below the desired IED in...

Page 40: ...s Note that normally Refresh Values will only affect the visible parameters to make the operation faster In order to update also hidden collapsed parameters click the checkbox next to the button This...

Page 41: ...en the Commit and Reject buttons will not appear and the changes will only be temporary Parameter Set selection restores the old value until the new value has been stored permanently or temporarily IE...

Page 42: ...the Active Setting Group parameter To change the parameter follow steps 2 5 COM600_PST_setting_group png Figure 3 11 1 3 Selecting a setting group Measurements 3 12 Viewing measurements 3 12 1 To vie...

Page 43: ...surement configuration as the bay object However only measurements originating from the IED are shown If bay measurements are not configured IED measurements are populated automatically measnewied png...

Page 44: ...m events with the records Each fault record is marked with an up counting fault number and a time stamp that is taken from the beginning of the fault The amount of information in a fault record depend...

Page 45: ...To view a certain record select it from the list FaultRecord png Figure 3 13 1 Fault record view 45 COM600 series 5 1 1MRS756705 Operator s Manual...

Page 46: ...node under the desired object WebHMI updates the values in tables automatically according to the configuration summary tablePicture 1 png Figure 3 14 1 Summary Table The tables are separated into dif...

Page 47: ...ndicator on off auto matic manual X not X and so on It can also be used to send a command Two State Switch Hyperlink to external information source such as a web page or a local file on COM600 Files s...

Page 48: ...IED Multiple State Button ViaPoint Connectivity Node Circuit breaker Inter mediate position Circuit breaker Open position Circuit breaker Closed position Circuit breaker Bad faulty position Disconnect...

Page 49: ...h two Windings and no Tap Changer Primary winding on top Second ary winding below All composing elements exist as individual sym bols Power Transformer with two Windings and Tap Changer Primary windin...

Page 50: ...citor Reactor Generator Motor In feeder Out feeder Earth symbol Bay Switch Indicator Station Switch Indicator Display Voltage Five State Switch Left Earthed Five State Switch Right Earthed Power Cable...

Page 51: ...stituted BL OperatorBlocked OoR OutOfRange OSC Oscillatory NT OldData NC Inconsistent NA Inaccurate OV Overflow BadRef BadReference IV Failure BadTime BadTime SubNormal SubNormal CfgErr ConfigError No...

Page 52: ...52...

Page 53: ...ring general 29 modes 30 C Capacitor Bank 28 communication structure 17 D Data Historian 36 device information 18 diagnostics information 18 disturbance recordings 37 document library 17 E event infor...

Page 54: ...39 Q quality flag 51 S Single Line Diagram general 19 multiple views 20 symbols 47 substation summary table 46 substation structure 16 Switch Device Control 20 T tap changer 27 U users adding 14 chan...

Page 55: ......

Page 56: ...Phone 358 10 22 11 ABB Distribution Automation 4300 Coral Ridge Drive Coral Springs Florida 33065 Phone 1 954 752 6700 www abb com mediumvoltage www abb com substationautomation 1MRS756705 G 28 3 2018...