background image

LIAF299-1

ICM

2909

Direct Spark Ignition (DSI) control board

Features

 Direct Spark Ignition (DSI) control board

 Microprocessor-based

 Monitors timing, trial for ignition, system switches, flame sensing and 

lockout.

 100% lockout safety feature

 Compatible with LP or Natural Gas

 LED indication for status and fault codes to aid in troubleshooting

Specifications

Replaces

• 

Rheem: 

62-23599(-01,-02,-03,-04,-05)

ELECTRICAL SHOCK HAZARD! 

Before installing this unit, turn 

off power at the main service panel by removing the fuse or switching the 

appropriate circuit breaker to the OFF position. Follow all Local, State and 

National Electrical Codes when installing this device.

CAUTION!

 

Only trained personnel should install or service heating 

equipment. When working with heating equipment, be sure to read and 

understand all precautions in the documentation, on labels, and on tags that 

accompany the equipment. Failure to follow all safety guidelines may result in 

damage to equipment, severe personal injury or death.

> > > CAUTION < < <

Introduction

The 

ICM2909

 DSI control replaces the following Rheem models: 62-23599(-01,-02,-03,-

04,-05). The 

ICM2909

 has incorporated LED diagnostics to assist in troubleshooting. Fault 

code information can be found in this application guide. Please keep this application guide 

with the furnace installation manual for future reference.

Remove Existing Control

CAUTION!

 

To service control, and prior to disconnection, label all wires. Failure 

to do so may result in wiring errors that can cause dangerous operation.

1.  Turn thermostat to the OFF position or set it to the lowest possible setting.
2.  Turn OFF the electrical supply to furnace.
3.  Turn OFF the gas supply to furnace.

CAUTION! 

Failure to turn off gas and electric supplies can result in explosion, 

fire, death or personal injury.

4.  Remove the furnace blower and control access doors.

5.  Disconnect the thermostat wires and humidifier wires (if equipped with a humidifier).
6.  Disconnect the line voltage, blower, electronic air cleaner wires (if equipped) and 

transformer wires.

7.  Remove screws and any other fasteners and the old circuit board.
8.  Examine the control and the control box for water stains.

9.  Make repairs if any sources of water leakage are found. Be sure to check humidifiers, 

evaporator coils and vent systems in the area of the control.

Install New Control

1. Ground yourself. When handling the circuit board; hold it by the edges.

2. Fasten the circuit board with the retaining screws.

3. Connect all line voltage, low voltage and accessory wires.

4. Verify the sequence of operation.

Sequence of Operation

When a W call is received from the thermostat; the control shall perform a hardware safety 

check before progressing with the heat sequence. If no issues are detected during the 

hardware safety check; the Inducer Draft motor is energized. The Vent Pressure switch 

closes. Ignition sequence begins; gas valve and spark are engaged, providing the system 

safety switches (Limit and MRLC) are closed. The Blower motor will engage at the 

HEAT

 

speed 

30 seconds after flame is established and sensed. Once the W call has been 

satisfied; the Inducer motor turns off after 5 seconds and the blower motor turns off after 90 

seconds

.

A G call from the thermostat will engage the blower motor without delay at the 

HEAT

 speed. 

It disengages without delay when the G call is removed.
A Y call from the thermostat will engage the blower motor without delay at the 

COOL

 

speed. It disengages 

30 seconds after the Y call is satisfied.

Flame Sense Troubleshooting Tips

Flame not established

1.  If flame is not established during the 7 second initial sequence then the control will start 

the next trial for ignition in 

60 seconds

.

2.  There will be 2 more attempts to ignite, 

60 seconds

 apart before the respective fault 

code is triggered and ignition trials are stopped.

3.  The gas valve is energized only during the ignition sequence of 7 seconds

.

4.  The blower motor is off until 

30 seconds after flame is established.

Flame out

1.  Flame out is considered when flame is lost during the heating cycle.

2.  When a signal is present on W and flame is not sensed; the gas valve will disengage 

until the next trial for ignition

3.  The inducer motor will continue running during flame out scenario and the blower motor 

will turn off after the 

90 second

 post purge.

Flame out of sequence

1.  Flame out of sequence represents a scenario where flame is sensed while the W signal 

is not present.

2.  Inducer and Blower motors will be engaged (if not already running) and will continue 

running for as long as the fault condition is present.

3.  There is 

60 minute

 lockout before a W call can be executed or on power reset

Inputs

• Line voltage: 

240 VAC, 50/60 Hz

• Control voltage: 

18-30 VAC, 50/60 Hz

• System switches:

 

Vent pressure, limit and MRLC (Manual Reset Limit Control)

Outputs

• Heat N.C.: 

16FLA/36 LRA @ 240 VAC

• Cool N.O.:

 

15FLA/30 LRA @ 240 VAC

• Inducer: 

4FLA/4LRA  @ 240 VAC

• Gas valve: 

2.3 A PILOT DUTY @ 240 VAC

  

Environmental

• Operating temperature: 

-40˚F to 175˚F (-40˚C to 80˚C)

• Storage temperature: -

40˚F to 185˚F (-40˚C to 85˚C)

• Humidity: 

5% - 95% R.H. (non-condensing) at +55˚C

• Dimensions: 

6.60” x 5.75” x 2.25”

5018419

FAULT CODES, STATUS LIGHTS AND TROUBLESHOOTING

Flashes

Fault Condition

Trouble Shooting

ON solid

Normal operation

Normal

OFF 

No power or incorrect gas valve wiring

Check for 24VAC to the board,check door switch, check supply transformer primary and secondary voltage, make sure gas 

valve is wired correctly and grounded properly.

1

Flame loss or ignition failure lockout

Flame was lost or the number of retry’s or recycles has exceeded the limit for the control. Clean or replace the flame sensor, 

check the igniter for proper operation & input voltage, check the transformer’s common is grounded to earthground

2

Pressure switch stuck open or stuck 

closed

Check for obstructed pressure switch tubing or defective pressure switch. Check for oxidation on terminals, broken wires, or  

defective inducer motor. Check for proper voltage at the inducer motor input.

3

Limit switch open

Check for blocked airflow, blocked duct work and dirty filter. Check or replace high limit switch if defective.

4

Flame detected with gas valve closed

Flame was sensed when no flame is present. Check or replace flame sensor and check the grounds.

5

Manual Reset Limit Control is open

Check for plugged flue pipe, check for cracked heat exchanger, check for flame rollout.

6

Internal Error

Internal board failure, replace control board

Reviews: