Maintenance-Object Repair Procedures
555-233-143
8-32
Issue 1 May 2002
1001
ABORT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1002
ABORT
The system could not allocate time slots for the test. The system may be under
heavy traffic conditions, or it may have time slots that are out-of-service due to
TDM-BUS errors.
1. If the system has no TDM-BUS errors and is not handling heavy traffic,
retry the command at 1-minute intervals up to 5 times.
1003
ABORT
The system could not allocate a tone receiver for the test. The system may be
oversized for the number of Tone Detectors present, or some Tone Detectors
may be out of service.
1. Resolve any TTR-LEV errors.
2. Resolve any TONE-PT errors.
3. Retry the command at 1-minute intervals up to 5 times.
1004
ABORT
The port was put in use during the test. The test has been aborted.
1. Use display port UUCSSpp to determine the voice port extension of the
port. Use status station command to determine the service state of the
port. If the port is active, wait until it is idle before retesting.
2000
ABORT
Response to the test request was not received within the allowable time period.
1. Retry the command at 1-minute intervals up to 5 times.
2100
ABORT
Could not allocate the necessary system resources for this test.
1. Retry the command at 1-minute intervals up to 5 times.
7
FAIL
Conference test failed on the primary channel. In some cases, users may not
notice a disruption in service. In extreme cases, the conferencing feature may
not work at all.
14
FAIL
The primary voice channel is not transmitting properly. User impact may range
from no noticeable effect to loss of use of this port.
15
FAIL
The control channel between the processor and AUDIX is not transmitting
properly. User impact may range from no noticeable effect to loss of use of this
port. This failure could also be disruptive to other users.
16
FAIL
The secondary voice channel is not transmitting properly. User impact may
range from no noticeable effect to loss of use of this port.
Table 8-11.
Test #13 Voice and Control Channel Local Loop Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...