Maintenance-Object Repair Procedures
555-233-143
8-1488
Issue 1 May 2002
142
FAIL
The SNI circuit pack has a fiber out-of-frame condition, but no loss of signal
condition. Also, no lightwave transceiver is connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber-link if no DS1C
complex is administered (check via list fiber-link). Otherwise, if a DS1C
complex is administered, the connected circuit pack is the DS1C circuit
pack connected to the SNI circuit pack.
2. If a lightwave transceiver is not supposed to be present, go to step 2. For
example, an SNI connected to a DS1C circuit pack or an SNI with a
metallic connection does not have a lightwave transceiver. Otherwise,
check the lightwave transceiver connections. If OK, replace the lightwave
transceiver. If a fiber out-of-frame condition exists and lightwave
transceivers are used, check that the lightwave transceivers are of the
same type, that is, both are 9823a or both are 9823b. If they are not the
same type, replace one of the lightwave transceivers:
■
9823a is used for distances up to 4900 feet.
■
9823b is used for distances up to 25,000 feet.
3. Perform the Fiber Fault Isolation Procedure described in Chapter 5.
4. Replace this SNI circuit pack.
5. Replace the connected circuit pack.
143
FAIL
The SNI circuit pack has a loss of signal condition, but no fiber out of frame
condition. Also, a lightwave transceiver is connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber-link if no DS1C
complex is administered (check via list fiber-link). Otherwise, if a DS1C
complex is administered, the connected circuit pack is the DS1C circuit
pack connected to the SNI circuit pack.
2. Perform the Fiber Fault Isolation Procedure described in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
Table 8-583.
TEST #989 SNI Fiber Out of Frame Query —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...