AN-LN-PT (Analog Line Port)
Issue 1 May 2002
8-115
555-233-143
1008
ABORT
A ringing circuit could not be allocated. Either every ringing circuit is active, the
ringing generator is defective, or it is incorrectly wired.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort, look for RING-GEN errors in the Error Log.
3. If ABORT 1008 occurs for this test on other circuit packs as well, the
ringing generator may be defective or is incorrectly wired (see
.
4. If an ABORT 1008 does not occur on other ports, then all four ring phases
are active.
1018
ABORT
Administration has disabled the test. The default for the
Test?
field on the
station form is y. Determine why this field has been set to n on this station (this
may be due to the ringing application Test 48, which can be disturbing to
customer or terminal equipment).
1. To enable the test for a particular station being tested, enter change
station extension.
2. Change the
Test?
field on the station form to y.
2000
ABORT
Response to the test request was not received within the allowable time period.
2100
ABORT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort, escalate the problem.
FAIL
The terminal equipment is not connected to the circuit pack. Some terminal
equipment, such as modems, may fail even when connected properly.
1. Remotely test the terminal equipment.
2. If the test fails again, resolve any RING-GEN errors in the error log, if
present.
3. Check all of the wiring between the station equipment and the switch.
Then, run the test again.
4. If the test still fails, the terminal equipment may be defective. Check and
replace it, if necessary.
5. Some terminal equipment might fail even when it is connected properly. If
this is the case, disable the test using the change station extension
command (enter n into the
Test
field). Note that this action also disables
Tests 6, 7, 35, and 161 on this port.
Table 8-44.
Test #48 Station Present Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...