Maintenance-Object Repair Procedures
555-233-143
8-1870
Issue 1 May 2002
Conference Circuit Test (#7)
The Conference Circuit test verifies that the NPE channel for the port being tested
can correctly perform the conferencing function. The NPE is instructed to listen to
several different tones and conference the tones together. The resulting signal is
then measured by a Tone Detector port. If the level of the tone is within a certain
range, the test passes.
Table 8-718.
Test #7 Conference Circuit Test
Error
Code
Test
Result
Description / Recommendation
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1000
ABORT
System resources required to run this test are not available. The port may be
in use on a valid call. Use the status access-endpoint extension command to
determine when the port is available for testing.
1004
ABORT
The port has been seized by a user for a valid call. Use the status
access-endpoint extension command to determine when the port is available
for testing. The port is available when it is in the in-service/idle state.
1. Retry the command at 1-minute intervals up to 5 times.
1020
ABORT
The test did not run due to a previously existing error on the specific port or
because of a more general circuit pack error.
1. Examine the Error Log for existing errors against this port or circuit pack,
and attempt to diagnose the previously existing error.
2000
ABORT
Response to the test was not received within the allowable time period.
2100
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
The NPE of the tested port did not conference the tones correctly. This causes
noisy and unreliable connections. Even though wideband calls do not use the
conferencing feature on the NPE, this failure indicates problems with the circuit
pack hardware.
1. Replace the circuit pack.
PASS
The port can correctly conference multiple connections.
1. Investigate user-reported troubles on this port using other port tests and by
examining the terminal adapter or external wiring.
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...