Maintenance-Object Repair Procedures
555-233-143
8-1496
Issue 1 May 2002
STRAT-3 (Stratum-3 Clock)
The Digital Synchronization Network Plan (PUB 60110) specifies a hierarchy of
synchronization nodes consisting of Strata 1 to 4, where the public network’s sole
Stratum-1 clock is the most accurate. The Release 5r system supports both
Stratum-3 and -4 operations. See
‘‘Stratum-4 Synchronization’’ on page 8-1511
for details on Stratum-4 operation.
A Stratum-3 clock derives its timing from two DS1 references connected to a
Stratum-3 or better source. The Stratum-3 clock provides a holdover of at least
24 hours should both DS1 references fail. (After 24 hours, the Stratum-3 clock
still provides service but its accuracy may be degraded). The Digital
Synchronization Network Plan (PUB 60110) requires that the Stratum-3 clock
have duplicated components.
The Stratum-3 clock can be configured with only one DS1 input if one of the Clock
Input cards is removed. Also, the Stratum-3 clock can free run (use its internal
clock without using DS1 inputs, if both Clock Input cards are removed).
Only a TN780 Tone-Clock circuit pack recognizes and supports a Stratum-3 clock
and its alarm signals. (The TN780 Tone-Clock circuit pack is also backward-
compatible with a TN768 Tone-Clock circuit pack.) The Stratum-3 clock may be
connected to a non-IPSI EPN where a TN780 Tone-Clock circuit pack resides.
The Stratum-3 clock should never be connected to an IPSI-connected EPN.
The only operation that software can perform is a query of the alarm leads. The
only recovery action that can be performed on a catastrophic failure of the
Stratum-3 clock is using the local oscillator on the active TN780 Tone-Clock circuit
pack. Neither software nor the TN780 Tone-Clock circuit pack can request
additional information about the health of the Stratum-3 clock other than the
information provided by the alarm leads. Furthermore, neither the software nor
the TN780 Tone-Clock circuit pack can request that the external clock switch
references, change configuration, disable/enable, initialize, and so forth.
In the system, the Stratum-3 clock has been implemented as an external which
follows the specification in PUB 60110 for Stratum 3. The only external Stratum-3
clock that is supported is the Telecom Solutions Digital Clock Distributor
™
for
Customer Premise Timing (DCD-CPT) Stratum-3 clock.
shows how the Stratum-3 hardware configuration provides clock and
alarm signals to the TN780 Tone-Clock circuit pack(s). The reference DS1
facilities connect directly to the Stratum-3 clock for timing purposes, but the DS1
data may be routed into the switch by using a Y connector (H-600-274 G1 for the
50-pin DS1 end or H-600-274 G2 for the 15-pin DS1 end).
MO’s Name (in
Alarm Log)
Alarm Level
Initial SAT Command to
Run
Full Name of MO
STRAT-3
MAJOR
test synchronization
Stratum-3 clock
STRAT-3
MINOR
test synchronization
Stratum-3 Clock
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...