FIBER-LK (Fiber Link)
Issue 1 May 2002
8-865
555-233-143
143
FAIL
The SNI circuit pack (Endpoint 1 of the fiber link) has a loss-of-signal condition,
but no fiber out-of-frame condition. Also, a lightwave transceiver is connected
to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
2. Perform the
‘‘Fault Isolation for Fiber Links’’ on page 4-19
in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
144
FAIL
The SNI circuit pack (Endpoint 1 of the fiber link) has a loss-of-signal condition,
but no fiber out-of-frame condition. Also, no lightwave transceiver is connected
to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
2. Perform the
‘‘Fault Isolation for Fiber Links’’ on page 4-19
in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
145
FAIL
The SNI circuit pack (Endpoint 1 of the fiber link) has a fiber out-of-frame
condition and a loss-of-signal condition. Also, a lightwave transceiver is
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
connected circuit pack is the other endpoint of the fiber-link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
2. Perform the
‘‘Fault Isolation for Fiber Links’’ on page 4-19
in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
Table 8-331.
Test #989 SNI Fiber Out of Frame Query —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...