Maintenance-Object Repair Procedures
555-233-143
8-1292
Issue 1 May 2002
PNC Interchanges
PNC spontaneous interchanges occur when PNC duplication software determines
that the SOH of the standby PNC is better than that of the active PNC. PNC-DUP
executes a spontaneous interchange only when a message from a PNC
component MO sends a message indicating that either a fault has occurred on the
active PNC, or a fault has been resolved on the standby PNC such that the state
of health of the active PNC is now lower than that of the standby.
This message will usually indicate the type and location of the failed connectivity
component. A corresponding major or minor alarm is logged by the reporting MO,
stimulating an alarm report.
In the less common situation when the resolution of a fault on the standby renders
it more healthy than a simultaneously faulted active PNC, the message will
indicate the type and location of the improved component.
Once the interchange completes, the failed component will be on the standby
PNC. A demand interchange can be requested in the presence or absence of
standby PNC faults. The following sequence of actions can be observed during a
fault-free interchange:
1. The Expansion Interfaces currently acting as archangels in the PNs are
deactivated as indicated by the amber LEDs going from flashing to on
solid.
2. The EIs in IPSI port networks are interchanged as indicated by the new
standby EI amber LED off and the new active EI amber LED on solid.
3. One by one the EIs in non-IPSI port networks are interchanged as
indicated by new standby EI amber LED turning off and the new active EI
amber LED flashing (2 seconds on, 200 milliseconds off). At this point the
interchange is functionally complete.
4. The SNIs amber LEDs are updated. so that the SNIs on the active SN
have amber LEDs on, while the standby SN’s SNIs amber LEDs turn off.
Certain conditions may interfere with the normal execution of the interchange:
1. In a faulted spontaneous interchange it is possible the PN directly affected
by the fault will be the last to interchange.
2. A user directly affected by the single fault instigating a PNC interchange
can experience a momentary outage of voice path connectivity during the
switch.
3. If faults exist on both the standby and active PNC, it is possible to have
some PNs go out of service while others are returned to service.
4. The new standby SNIs amber LED my not be off due to a fault in the line of
communication path to the standby SNIs. In a multi-fault interchange,
LEDs on the new active SNIs may not be on for the same reason.
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...