Maintenance-Object Repair Procedures
555-233-143
8-844
Issue 1 May 2002
Table 8-328.
Test #759 Configuration Audit
Error
Code
Test
Result
Description / Recommendation
2100
ABORT
Could not allocate the necessary system resources to run this test for
endpoint 1 of the fiber link. (The list fiber-link command displays a fiber link’s
endpoints.) If this fiber link has two SNI endpoints, run the test board UUCSS
test separately for each SNI and follow the repair procedures in section
SNI-BD.
2300
ABORT
The downlink message necessary to run this test could not be sent. If this fiber
link has two SNI endpoints, run the test board UUCSS test separately for each
SNI and follow the repair procedures in section SNI-BD (list fiber-link can be
used to display fiber link endpoints).
2301
ABORT
The software timer could not be set before sending the downlink message
necessary to run this test. If this fiber link has two SNI endpoints, run the test
board UUCSS test separately for each SNI and follow the repair procedures in
section SNI-BD (list fiber-link can be used to display fiber link endpoints).
1. Retry the command at 1-minute intervals up to 3 times.
2306
ABORT
An SNI circuit pack on the fiber link is not responding to test requests sent by
software.
1. Run the test led switch-node for the switch node(s) where the SNI(s)
reside to verify whether the LEDs on the board(s) light. Follow the steps
below for the SNI(s) that had no LEDs light.
2. If the LEDs on the other boards in the carrier light, but the LEDs on this
board do not light, run Test #760 via test board UUCSS l for the active
SNC in this carrier. Wait 5 minutes and then try step 1 one more time. If
the LEDs on this board still do not light, replace the board. (Replacing an
SNI may be service interrupting. Refer to the SNI-BD section for the
procedure to replace an SNI.)
3. If none of the LEDs light for the boards in the same carrier as this board, fix
any problems associated with the connectivity of this carrier to the media
server. Use list fiber-link to determine the fiber connections to this carrier.
Check the LEDs on every SNI and EI, and fix any fiber problems. Enter
display errors and resolve any EXP-INTF error entries associated with
the PN. Also, resolve any SYNC, SNI-BD, SNC-BD, FIBER-LK, or
SNI-PEER error entries.
2500
ABORT
Internal system error If this fiber link has two SNI endpoints, run the test board
UUCSS test separately for each SNI and follow the repair procedures in
section SNI-BD. (The list fiber-link command displays a fiber link’s
endpoints.) Otherwise:
1. Retry the command at 1-minute intervals up to 3 times.
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...