SYS-PRNT (System Printer)
Issue 1 May 2002
8-1539
555-233-143
SYS-PRNT (System Printer)
The Report Scheduler feature provides the capability to schedule printing of
output form selected administration commands on an asynchronous System
Printer (SYS-PRNT) or a Personal Computer (PC). The System Printer device
connects to the system via a data module (PDM, MPDM, DTDM) connected to a
port on a TN754 Digital Line circuit pack which is administered as a data
extension. A System Printer device can also be connected through an ADU to a
port on TN726B Data Line circuit pack. The System Printer link to the processor
is via a C-LAN board. For information about C-LAN connectivity, see
(Control LAN Circuit Pack)’’ on page 8-411
System Printer Link Maintenance provides a strategy for maintaining the link
between the system and an external SYS-PRNT output device. The strategy
includes a set of tests for detection of errors during normal operation,
troubleshooting actions, and alarms for serious problems. System Printer Link
Maintenance uses a try-and-wait mechanism for maintaining the SYS-PRNT link.
A minor alarm is raised when the link set-up fails. A warning alarm is raised when
the server has been busied out. up to two link retry attempts is made. After the
second attempt, set-up attempts are only made by the application software. (The
15-minute timer fires and jobs are printed unless an immediate job was entered.)
After two unsuccessful attempts to establish the link, a MINOR alarm is raised. If
the System Printer Link is torn down due to an error, System Printer Link
Maintenance will raise a MINOR alarm but will not attempt to bring up the System
Printer Link.
System Printer Link Maintenance does not cover the elements comprising the
SYS-PRNT physical link: the external SYS-PRNT output device, the Data Module
(PDM/MPDM/DTDM) and TN754 Digital Line, or the ADU and TN726B Data Line.
If System Printer Link Maintenance cannot restore the System Printer Link, the
maintenance tests of these individual components of the System Printer Link must
be executed to diagnose faults.
MO’s Name As It
Appears in Alarm
Log
Alarm
Level
Initial System Technician
SAT Command to Run
Full Name of
MO
SYS-PRNT
MINOR
test sp-link l
System Printer
SYS-PRNT
WARNING
release sp-link
System Printer
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...