UDS1-BD (UDS1 Interface Circuit Pack)
Issue 1 May 2002
8-1749
555-233-143
Blue Alarm Inquiry Test (#139)
The Blue Alarm is a signal sent by the remote DS1 endpoint when it is
out-of-service. The Blue Alarm Inquiry test checks the blue alarm status of the
remote DS1 endpoint.
When the UDS1 Interface circuit pack detects a Blue Alarm signal from the
remote DS1 endpoint, the circuit pack transmits a Yellow alarm to the remote DS1
endpoint and sends a BLUE ALARM message to the maintenance software.
When the Blue alarm is confirmed, the maintenance software places every trunk
or port of the UDS1 Interface circuit pack into the out-of-service state. The inquiry
test runs every 10 minutes until the Blue alarm is cleared.
The UDS1 Interface circuit pack takes one second to recognize and report a Blue
alarm and 16 seconds to recognize and report the resolution of a Blue alarm.
When the Blue alarm is cleared, the UDS1 Interface circuit pack stops transmitting
the Yellow alarm and places the trunks or ports back into the service state before
the Blue alarm occurs.
Line Loop-Back Alarm
The LLB (Line Loopback) is used by the remote DS1 endpoint to put the ICSU or
DS1 board into a loop-back mode. When the ICSU or DS1 board is in the LLB
mode, the arriving bit pattern is regenerated and sent back. The LLB Alarm
activates when the in-band activate LLB bit pattern arrives continuously for
5 seconds on the DS1 line. The LLB deactivates when the in-band deactivate
LLB bit pattern arrives continuously for 5 seconds on the DS1 line.
Since LLB is a maintenance condition rendering every DS0 channel unavailable
for signaling or bearer traffic, maintenance software treats this the same as a Blue
Alarm.
Payload Loopback Alarm
The PLB (Payload Loopback) is used by the remote DS1 endpoint to put the
switch DS1 into a loop-back mode. The PLB Alarm activates when a network
protocol activate bit pattern arrives over the 4-Kbps ESF data link on the DS1 line.
The PLB deactivates when a network protocol deactivate bit pattern arrives over
the 4-Kbps ESF data link on the DS1 line.
Since PLB is a maintenance condition rendering every DS0 channel unavailable
for signaling or bearer traffic, maintenance software treats this the same as a Blue
Alarm.
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...