ATM-SGRP (ATM Signaling Group)
Issue 1 May 2002
8-263
555-233-143
Table 8-110.
Test #1291 Remote Layer 3 Query
Error
Code
Test
Result
Description / Recommendation
1006
ABORT
There are no associated B channels in an ISDN “in-service” or “maintenance”
service state. This is a NORMAL ABORT.
1. Administer or release an ISDN trunk or PRI endpoint before retrying the
test. For an ATM trunk, use the status trunk grp#/mbr# command to
verify the ISDN trunk state.
2. Retry this test when at least one B channel is in the “in-service” or
“maintenance” states.
1113
ABORT
The signaling channel is down. Therefore, no messages can be sent to the
far-end switch or terminal adapter.
1. Examine the results of Test #636, and follow recommendations provided
there.
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
2500,
none
ABORT
Internal system error or administration problem
1. Determine whether any B channels are administered.
2. If there are none, then this is a normal ABORT, since this test cannot run
unless at least one B channel is administered.
3. If at least one B channel is administered, there is an internal system error.
Retry the command at 1-minute intervals up to 5 times.
FAIL
Internal system error
1. See description of ABORT with Error Code 2500.
PASS
A message was sent to the far-end switch or terminal adapter. The ISDN PRI
specification allows up to 2 minutes for a reply.
1. Check the Error Log for ATM-SGRP errors of type 2305 for evidence of a
Remote Layer 3 Query failure.
2. If no new errors were logged since this test was run, then this switch and
the far-end switch can exchange call control messages.
3. If there is still a problem with a particular ATM trunk, busyout the trunk and
run the long test sequence, paying particular attention to the results of Test
#258 (ISDN test call).
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...