AC-POWER
Issue 1 May 2002
8-7
555-233-143
AC Power Query Test (#78)
This test queries either the server’s watchdog (via an Ethernet or USB interface)
or an MCC EPN’s Maintenance circuit pack for status of the cabinet’s AC power.
Table 8-2.
Test #78 Power Query Test
Error
Code
Test
Result
Description / Recommendation
1000
ABORT
System resources required to run test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
100,
2000
ABORT
Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to ABORT with error code 2000, check for system
powering problems with the EPN’s A carrier. Resolve every AC-POWER
and CARR-POW alarm. Then, repeat the test.
3. If the test still ABORTs with error code 2000, check for and resolve every
MAINT (Maintenance circuit pack) error in an EPN. Then, repeat the test.
2029,
2319,
2320,
2500
ABORT
Internal system error
1
FAIL
NOTE:
For a J58890CE, skip to step 2.
1. Procedures for a Global MCC (J58890CH):
a. For a nominal holdover system if there is no AC power at the wall
outlet, have a qualified electrician restore power to the outlet. Power
should range from 170 to 264 VAC.
b. If there is AC power at the wall outlet, then there could be a problem
with the RM0850 rectifiers, BU3200A BIU (battery interface unit), or
battery. Resolve every alarm logged against the POWER MO, and
rerun the test. If the test still fails, the BIU may be defective. Check
the BIU. If the BOD alarm LED is on, replace the BIU.
If the BOD LED is off and the BOK LED is on, then an EPN’s
Maintenance circuit pack may be incorrectly reporting the problem.
Resolve every alarm against these MOs, and rerun the test.
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...