Maintenance-Object Repair Procedures
555-233-143
8-1472
Issue 1 May 2002
Packet Neighbor Link Test (#767)
This test is nondestructive.
This test checks the packet path of the neighbor circuit pack and the peer circuit
packs. A packet is sent from the SNI being tested to the peer SNIs and to the
neighbor EI or SNI. If the other EI or SNI sends the same data back in the packet,
this test passes. Otherwise, this test fails.
Table 8-581.
TEST #767 Packet Neighbor Link Test
Error
Code
Test
Result
Description / Recommendation
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2300
ABORT
The downlink message necessary to run this test could not be sent.
1. Retry the command at 1-minute intervals up to 3 times.
2301
ABORT
The software timer could not be set before sending the downlink message
necessary to run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2302
ABORT
Software received incorrect message data from the SNI circuit pack.
1. Retry the command at 1-minute intervals up to 3 times.
2303
ABORT
The SNI circuit pack responded that the software test requested is invalid.
1. Retry the command at 1-minute intervals up to 3 times.
2304
ABORT
SNI firmware is not able to run the test. For this particular test, the SNI circuit
pack must be able to communicate with its neighbor.
1. Verify that the SNI can communicate with its neighbor by checking the
yellow LED of the SNI to make sure the SNI is in frame or by running the
test board command for the SNI and checking test 989 for fiber
out-of-frame. If the results of Test 989 indicate that the fiber is
out-of-frame, follow the recommendation associated with the test failure. If
a DS1 converter complex exists on the fiber link, enter display errors and
follow the associated repair procedures for any DS1C-BD and DS1-FAC
entries.
2. Retry the command at 1-minute intervals up to 3 times.
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...