ANL-LINE, ANL-NE-L (8-Port Analog Line)
Issue 1 May 2002
8-85
555-233-143
1004
ABORT
The port was seized by a valid call during the test. The test has been aborted.
1. Use the display port UUCSSpp command to determine the station
extension. Use the status station command to determine the service
state of the port. If the service state indicates that the port is active, then
the port is unavailable for certain tests. Wait until the port is idle before
retesting.
2. Retry the command at 1-minute intervals up to 5 times.
3. If the test continues to abort and the port is idle, escalate the problem.
1005
ABORT
The test was aborted due to a configuration problem. This code occurs under
either of the following conditions:
■
This test may not be applicable, or it may be disruptive to terminal
equipment other than a voice terminal (for example, a modem pool
member or music on hold).
■
The circuit pack is one of the following:
— TN742 vintage 13, 14, or 15
— TN769 vintage 3, 4, or 5
1018
ABORT
Test disabled via administration. The default for the
Test?
field on the station
form is y; thus, you may want to determine why this field has been set to n on
this station (this may be due to the ringing application test 48, which can be
customer or terminal disturbing).
1. To enable the test for a particular station, enter change station extension
and set the
Test?
field to y.
1020
ABORT
The test did not run due to a previously existing error on the specific port or a
more general circuit pack error.
1. Examine Error Log for existing errors against this port or the circuit pack
and attempt to diagnose the previously existing error.
2000
ABORT
Response to the test request was not received within the allowable time period.
2100
ABORT
System resources required to run this test are not available. Either a system
allocation to get information about the port or to put the port into a service state
failed or the attempt to put the port in connection with a tone source failed (this
could be a Tone-Clock problem). The Tone-Clock and Tone Detectors could
be having a communication problem. (For example, the companding modes
could be out of synchronization.)
1. Retry the command at 1-minute intervals up to 5 times.
Table 8-34.
Test #6 NPE Crosstalk Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...