ANL-LINE, ANL-NE-L (8-Port Analog Line)
Issue 1 May 2002
8-99
555-233-143
1005
ABORT
The test was aborted due to a configuration problem. This code occurs under
either of the following conditions:
1. This test may not be applicable, or it may be disruptive to terminal
equipment other than a voice terminal (for example, the modem pool
member or music on hold).
2. The circuit pack is one of the following:
— TN742 vintages 13, 14, and 15
— TN769 vintages 3, 4, and 5
1008
ABORT
Could not allocate a ringing circuit for one of the following reasons: (1) every
ringing circuit is active, or (2) the ringing generator is defective, or (3) it is
incorrectly wired.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort, look for RING-GEN errors in the Error Log. If
an ABORT 1008 occurs for Test #48 on other circuit packs as well, then the
ringing generator may be defective or incorrectly wired. If it does not occur
on other ports, then that circuit pack is currently using all four ringing
phases.
1018
ABORT
The test was disabled via administration. The default for the
Test?
field is y;
thus, you may want to determine why this field has been set to “n” on this
station (this may be due to the ringing application Test #48, which can be
customer or terminal disturbing).
1. To enable the test for a particular station, enter change station extension
and set the
Test?
field to y.
2000
ABORT
Response to the test request was not received within the allowable time period.
2100
ABORT
System resources required to run this test are not available. Either a system
allocation to get information about the port or to put the port into a service state
failed or the attempt to put the port in connection with a tone source failed (this
could be a Tone-Clock problem). The Tone-Clock and Tone Detectors could
be having a communication problem. (For example, the companding modes
could be out of synchronization.)
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort, escalate the problem.
Table 8-38.
Test #48 Station Present Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...