Maintenance-Object Repair Procedures
555-233-143
8-598
Issue 1 May 2002
Control Channel Loop-around Test (#52)
This test queries the circuit pack for its circuit pack code and vintage and verifies
its records.
Table 8-242.
Test #52 Control Channel Loop-around Test
Error
Code
Test
Result
Description / Recommendation
None
2100
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
The test failed because the circuit pack did not return the circuit pack code or
vintage.
NOTE:
Error type 1538 in the error log indicates hyperactivity. The hyperactive
circuit pack is out of service and one or more of the following symptoms
may be exhibited.
1. The DS1-BD tests (such as Tests 138 and 139) are aborting with error
code 2000.
2. The tests run on the ports of this circuit pack are returning a no board
result.
3. A busyout or a release command has no affect on the test result.
4. A list config command shows that the circuit pack and the ports are
properly installed.
NOTE:
When hyperactivity occurs, the circuit pack is isolated from the system,
and all of its trunks are placed into the out-of-service state. The system
will try to restore the circuit pack within 15 minutes. When no faults are
detected for 15 minutes, the DS1 interface circuit pack is restored to
normal operation. Every DS1 interface trunk is then returned to the
in-service state. Hyperactivity is often caused by the associated facility.
In such a case, faults (such as slips, misframes, or blue alarms) would
be entered in the error log. In addition, many hardware errors would be
logged against the associated trunk circuits. If the facility is OK and the
error occurs again after 15 minutes, escalate this problem.
1. Retry the command up to 5 times.
2. If the problem continues, check for hyperactivity. Resolve the problem, as
appropriate.
3. If there is no longer hyperactivity, retry the command up to 5 times.
4. If the test continues to fail, escalate this problem.
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...