Maintenance-Object Repair Procedures
555-233-143
8-1804
Issue 1 May 2002
2000
ABORT
Response to the test was not received within the allowable time period. This
may be due to hyperactivity. Error Type 1538 in the error log indicates
hyperactivity. The hyperactive circuit pack is out of service, and one or more of
the following symptoms may be exhibited.
1. The UDS1-BD tests (such as Tests #138 and #139) are aborting with error
code 2000.
2. The tests run on the ports of this circuit pack are returning a no-board
result.
3. A busyout or a release command has no effect on the test results.
4. A list config command shows that the circuit pack and its ports are
properly installed.
NOTE:
When hyperactivity occurs, the circuit pack is isolated from the system,
and all of its trunks are placed into the out-of-service state. The system
will try to restore the circuit pack within 15 minutes. When no faults are
detected for 15 minutes, the UDS1 interface circuit pack is restored to
normal operation. Every trunk for the UDS1 interface circuit pack is then
returned to the in-service state. Hyperactivity is often caused by the
associated facility. In such a case, faults (such as slips, misframes, or
blue alarms) would be entered in the error log. In addition, many
hardware errors would be logged against the associated trunk circuits. If
the facility is OK and the error occurs again after 15 minutes, replace the
circuit pack.
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
1313
FAIL
The UDS1 circuit pack could not deactivate the loopback through the Customer
Loop-Back Jack.
1. Retry the test ds1-loop UUCSS end-loopback/span-test command at
1-minute intervals up to 5 times.
1314
FAIL
The UDS1 circuit pack could not deactivate the loopback through the far-end
CSU.
1. Make sure that the far-end DS1 is installed if the far-end CSU is a 120A1
CSU module/T1 sync splitter.
2. Retry the test ds1-loop UUCSS end-loopback | span-test command at
1-minute intervals up to 5 times.
Table 8-689.
Test #1216 End Loopback/Span Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...