CO-TRK (Analog CO Trunk)
Issue 1 May 2002
8-461
555-233-143
2000
ABORT
Response to the test was not received within the allowable time period.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
Trunk was seized, but dial tone could not be detected.
1. Test every administered outgoing port on the board. Failure of 1 port
indicates a problem toward the CO.
2. If every port fails, see note below.
3. Check for errors on the TONE-BD or TONE-PT. Clear any errors found,
and repeat the test.
4. If the error has still not cleared, refer the problem to the CO.
5. If no service problems exist on the port, continue to use the port until the
circuit pack can be replaced (as a last resort). Perform a trunk test call to
see if the trunk is operable.
NOTE:
If the dial tone test fails for every port on a circuit pack, a -5 Volt power
problem is indicated. To investigate problems with a power unit, see
‘‘CARR-POW (Carrier Power Supply)’’
2002
FAIL
Seizure portion of test failed due to hardware problem. Fault is usually caused
by a disconnected trunk.
1. If the CO Demand Diagnostic test (#3) also failed, display the Hardware
Error Log. If the CO Demand Diagnostic test failed because it could not
detect ground (indicated by Error Type 1281 in the Hardware Error Log)
AND Error Type 3329 or 3585 appears in the Hardware Error Log (with the
same last occurred time as Error Type 1281 and 1537), replace the circuit
pack.
2. Check trunk wiring to ensure good connection; repeat test if wiring
correction made.
3. Locate another identical CO trunk and swap its wiring with the one under
test. Repeat test on both trunks, and determine whether problem follows
trunk or remains at original port. If problem follows trunk, refer problem to
CO. If problem remains at port, replace circuit pack and repeat test.
1009
PASS
Detected tone was not pure dial tone. No action required.
Table 8-185.
Test #0 Dial Tone Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...