Maintenance-Object Repair Procedures
555-233-143
8-38
Issue 1 May 2002
Any
FAIL
The NPE of the tested port was found to be transmitting in error. This causes
noisy and unreliable connections.
1. Replace the circuit pack.
PASS
The port is correctly using its allocated time slots. User-reported troubles on
this port should be investigated by using other port tests, by examining station
wiring, or by examining the station.
Table 8-13.
Test #6 NPE Crosstalk Test —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page