PKT-INT (Packet Interface)
Issue 1 May 2002
8-1265
555-233-143
256,
512,
768
(cont’d)
FAIL
(cont’d)
2. If error code 512 or 768 is reported for an active IPSI’s Packet Interface
circuit, the receive FIFO in the PKT-INT has overflowed. This may
indicate that additional IPSI circuit packs are required.
For the current hardware configuration, only one IPSI circuit pack is
allowed per PN. Escalate the problem if not corrected by the following
repair steps. Retry the command after one minute if the test continues to
fail.
a. If this is a high- or critical-reliability system and if the Packet Interface
circuit is on the active IPSI, enter set ipserver-interface to perform a
planned IPSI interchange. Replace the standby IPSI circuit pack.
b. Otherwise, replace the circuit pack at a time that would cause the least
service disruption.
3. If error code 512 or 768 is reported for a standby IPSI’s Packet Interface
circuit, replace the IPSI circuit pack.
1024–
1096
FAIL
The standby IPSI’s Packet Interface circuit has bad Translation RAM
locations. A MINOR alarm is generated when the number of bad locations is
from 1 and 4. A MAJOR alarm is generated if the number of bad locations is 5
or more. The MAJOR alarm prevents a planned IPSI interchange. (A planned
interchange may be administered to occur automatically every 24 hours, or it
may be requested by using the set ipserver-interface Uc command.)
1. If a MAJOR alarm is associated with this error, replace the alarmed IPSI
circuit pack.
2. If a MINOR alarm is associated with this error, replace the alarmed IPSI
circuit pack at a time that would cause the least disruption to service.
PASS
The media server can communicate with the IPSI circuit pack’s Packet
Interface circuit.
1. If problems are still reported on the circuit pack, check for failures using
the Private Loop-around test (#885) and Maintenance Loop-around test
(#886).
Table 8-512.
Test #887 Read and Clear Board Counters —
Continued
Error
Code
Test
Result
Description / Recommendation
Continued on next page
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...