list measurements clan ppp
Issue 1 May 2002
7-183
555-233-143
list measurements clan ppp
This command provides a 24-hour history of important packet-level statistics from
which you can infer some LAN performance characteristics. For example,
■
Invalid frames—the number of frames that are misaligned
■
CHAP failures—Challenge Handshake Authentication Protocol—the
number of attempts for ppp authentication that failed
■
High Cyclic Redundancy Check (CRC)—detects and corrects errors on
every frame) errors could suggest that the connection may be “noisy”
The 24-hour history gives the ability to look back at these measures.
Data is retrieved at 15-minute intervals for 24 hours for CRC, Invalid Frame, and
Chap Failures for PPP connections. If the data cannot be retrieved for the
15-minute interval,
N/A
displays in the field. The delta (the change from the last
inquiry) and the total are provided for each error count. After the occurrence of an
“N/A,” the delta equals the total.
Table 7-25.
list measurements command parameter
Action/Object
Qualifier
Qualifier Description
Permissions
Defaults
Feature
Interactions
list
measurements
clan ppp
UUCCSSpp
schedule
Link identifier (primary
or secondary)
Port Address
Report sent to printer
Command is validated
and then a scheduling
form displays to
schedule execution of
the command. The
command is then
placed in the command
queue and is executed
at the specified time.
The information
displayed by the
command is sent to the
system printer instead
of the screen.
1
Examples:
list measurements
clan ppp
list measurements
1.
Refer to the Report Scheduler and System Printer feature specification for more details.
init
inads
craft
customer
Primary
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...