EXP-INTF (Expansion Interface Circuit Pack)
Issue 1 May 2002
8-773
555-233-143
Notes:
a. This flashing state corresponds to error codes 769 and 770 from the
Hardware Error Log and indicates a failure of Test #238. These error
codes will usually be accompanied by error code 1281 (no Expansion
Interface or SNI detected on opposite end of fiber). This condition may be
caused by the absence of the neighbor EI or SNI circuit pack, a broken or
missing fiber, or a missing lightwave transceiver on either endpoint (EI or
SNI circuit pack).
b. This flashing state corresponds to error code 1281 from the Hardware
Error Log and indicates a failure of Test #237. This condition is usually due
to the failure of this EI circuit pack or a failed EI or SNI circuit pack
neighbor.
c. This is the normal state for an active PN EI circuit pack that is also the bus
master (Expansion Archangel) in the PN.
d. This is the normal state for an active EI circuit pack that is not the bus
master (Expansion Archangel) for an PN. This applies only in the Direct
Connect configuration where the EI circuit pack in an PN is connected via a
fiber link to an EI circuit pack in the other PN.
e. This is the normal state for a standby EI circuit pack in a PN.
NOTE:
In an PN, its TN775C Maintenance (MAINT) circuit pack monitors the sanity
of the EI circuit pack. If the EI circuit pack should cycle between sane and
insane several times, the Maintenance circuit pack will hold the EI circuit
pack reset. If a new EI circuit pack is installed in the PN, and the red LED
remains lit, the PN’s Maintenance circuit pack should be removed because it
may be holding the new EI circuit pack reset. This condition could present
itself if there is a link problem to the PN, and the PN experiences several PN
restarts. The Maintenance circuit pack may be reinstalled after the EI circuit
pack has been physically inserted and the EI circuit pack’s red LED has
gone off.
Table 8-300.
Expansion Interface Circuit Pack Amber LED Flashing
States
Condition
LED On
LED Off
Fiber Out-of-Frame (a)
0.1 second
0.1 second
In frame-No Neighbor (b)
0.5 second
0.5 second
Expansion Interface Active (c)
2 second
0.2 second
Expansion Interface Active (d)
solid on
never off
Expansion Interface Standby (e)
never on
solid off
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...