6-1-(14)
Parallel Interface
Section 6-1
Input Signals: Switching the Scene Group
CHECK
The ERR signal will turn ON if the command to switch scene groups is input
while there is no Memory Card mounted to the Memory Card slot 1.
Re-registering Models
Output Signals
Input Signals: Registering the Model Again
DI6
OFF
DI7
DI7 is the execution trigger.
After DI0 to DI6 are set, allow at least 1 ms before turning ON DI7. The
BUSY signal will be ON while the command is being executed.
After confirming that the BUSY signal is ON, turn OFF DI7, and finally turn
OFF DI0 to DI6.
Signal
Function
Signal
Function
DI0 to
DI4
Set the scene group number (0 to 31).
DI5
ON
DI6
ON
DI7
DI7 is the execution trigger.
After DI0 to DI6 are set, allow at least 1 ms before turning ON DI7. The
BUSY signal will be ON while the command is being executed.
After confirming that the BUSY signal is ON, turn OFF DI7, and finally turn
OFF DI0 to DI6.
BUSY
DI7
DI0 to 6
8 to 15
RUN
OFF
ON
OFF
ON
OFF
ON
Enter Run Mode
Exit Run Mode
Executing command
Signal
Function
RUN
ON while the Controller is in Run Mode.
BUSY
Indicates that the Controller is re-registering models.
Do not input the next command while the BUSY signal is ON. If another
command is input while the BUSY signal is ON, either the operation being
performed or the command that was input may not be properly executed.
Signal
Function
DI0 to
DI4
DI8 to
DI15
Set the unit number (0 to 31).
(See note.)
DI5
OFF