6-1-(4)
Parallel Interface
Section 6-1
Gate ON delay
Set the time from when the result is output to the paral-
lel interface to when the GATE signal is turned ON. This
time is used to wait until the data output becomes sta-
ble. Set a time between 1.0 and 1,000 ms that is longer
than the external device’s delay time. The default set-
ting is 1.0 ms.
Gate ON time
(Effective only when
output control is set to
None or Sync.output.)
Set the length of time that the GATE signal remains ON.
Set a value between 1.0 and 1,000 ms so that the
external device can read the measurement result. The
default setting is 5.0 ms.
Timeout
(Effective only when
handshaking is used.)
A timeout error will occur if there is no response from
the external device within the timeout time. Set a value
between 0.5 and 120.0 s. The default setting at 10.0 s.
Num. of delays
(Effective only with
Sync. output.)
Set the number of times the STEP signal turning ON
will be ignored from the time the STEP signal first turns
ON until that measurement result is output.
Item
Settings