The list of fault displays
Protective functions
6 - 6
Alarm
The inverter does not trip. An Alarm (LF) signal can also be output with a parameter setting.
Fault
●
A protective function trips the inverter and outputs a Fault (ALM) signal.
●
The data code is used for checking the fault detail via communication or with Pr. 997 "Fault
initiation".
Operation panel indication
Name
Data code
Refer to
page
FN
Fan alarm
⎯
FN2
Internal fan alarm
⎯
Tab. 6-6:
Alarm
Operation panel indication
Name
Data code
Refer to
page
E.OC1
Overcurrent trip during acceleration
16
(H10)
E.OC2
Overcurrent trip during constant speed
17
(H11)
E.OC3
Overcurrent trip during deceleration or stop
18
(H12)
E.OV1
Regenerative overvoltage trip during
acceleration
32
(H20)
E.OV2
Regenerative overvoltage trip during constant
speed
33
(H21)
E.OV3
Regenerative overvoltage trip during
deceleration or stop
34
(H22)
E.THT
Inverter overload trip (electronic thermal relay
function)
48
(H30)
E.THM
Motor overload trip (electronic thermal relay
function)
49
(H31)
E.FIN
Heatsink overheat
64
(H40)
E.IPF
Instantaneous power failure
80
(H50)
E.UVT
Undervoltage
81
(H51)
E.ILF
Input phase loss
82
(H52)
E.OLT
Stall prevention stop
96
(H60)
E. SOT
Loss of synchronism detection
97
(H61)
E.BE
Brake transistor alarm detection
112
(H70)
E.GF
Output side earth (ground) fault overcurrent
128
(H80)
E.LF
Output phase loss
129
(H81)
E.OHT
External thermal relay operation
144
(H90)
Tab. 6-7:
Fault (1)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......