Parameters
(E) Environment setting parameters
FR-A800
5 - 225
Life display of the cooling fan
●
If a cooling fan speed of less than the specified speed (refer below) is detected, Fan alarm
(FN) is displayed on the operation panel and the parameter unit. As an alarm display, Pr. 255 bit 2
is turned ON and also a warning is output to the Y90 signal and Alarm (LF) signal.
●
For the terminal used for the LF signal, set "98" (positive logic) or "198" (negative logic) in any of
Pr. 190 to Pr. 196 (output terminal function selection).
NOTES
When the main circuit capacitor life is measured under the following conditions, "forced end"
(Pr. 259 = "8") or", measurement error" (Pr. 259 = "9") may occur, or the status may remain in
"measurement start" (Pr. 259 = "1"). To perform measurement, first eliminate the following condi-
tions. Under the following conditions, even if "measurement complete" (Pr. 259 = "3") is reached,
measurement cannot be performed correctly.
●
FR-HC2, FR-CV, MT-RC, or a sine wave filter is connected.
●
Terminals R1/L11, S1/L21 or DC power supply is connected to terminals P/+ and N/-.
●
The power supply is switched ON during measurement.
●
The motor is not connected to the inverter.
●
The motor is running (coasting).
●
The motor capacity is smaller than the inverter capacity by two ranks or more.
●
The inverter is tripped or a fault occurred while the power was OFF.
●
The inverter output is shut off with the MRS signal.
●
The start command is given while measuring.
●
The applied motor setting is incorrect.
Operation environment: surrounding air temperature (annual average of 40 °C (free from corro-
sive gas, flammable gas, oil mist, dust and dirt)).
Output current (80% of the inverter rating)
Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent
starts and stops of the magnetic contactor must be avoided.
P
WARNING:
When measuring the main circuit capacitor capacity (Pr. 259 = "1"), the DC voltage is applied to
the motor for about 1 s at power OFF. Never touch the motor terminal, etc. right after powering
OFF to prevent an electric shock.
Capacity
Warning level
FR-A820-00250(3.7K) or lower, FR-A820-03160(55K) or higher
FR-A840-00126(3.7K) or lower
Less than 50% of the rated rotations
per minute
FR-A820-00340(5.5K) to FR-A820-02330(45K)
FR-A840-00170(5.5K) to FR-A840-03610(132K)
FR-A846-00250(7.5K) to FR-A826-00470(18.5K)
Less than 70% of the rated rotations
per minute
FR-A840-04320(160K) or higher
FR-A842-07700(315K) or higher
Approx. less than 1700 r/min
Tab. 5-92:
Warning level of different inverters
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......