Installation and wiring
Connection of motor with encoder (vector control)
FR-A800
2 - 71
To use a terminal as the terminal OH, assign the OH (external thermal O/L relay input) signal to an
input terminal. (Set "7" in any of Pr. 178 to Pr. 189. For details, refer to page 5-422.)
+
Assign the function using Pr. 178 to Pr. 184, Pr. 187 to Pr. 189 (input terminal function selection).
'
When position control is selected, terminal JOG function is invalid and simple position pulse train
input terminal becomes valid.
(
Assign the function using Pr. 190 to Pr. 194 (output terminal function selection).
Instructions for encoder cable wiring
●
Use shielded twisted pair cables (0.2 mm
2
or larger) to connect the FR-A8AP. For the wiring to the
terminals PG and SD, use several cables in parallel or use a thick cable, according to the wiring
length.
To protect the cables from noise, run them away from any source of noise (such as the main circuit
and power supply voltage).
When differential line driver is set and a wiring length is 30 m or more.
The wiring length can be extended to 100 m by increasing the 5 V power supply (approximately
to 5.5 V) while using six or more 0.2 mm
2
gauge cables in parallel or a 1.25 mm
2
or larger gauge
cable. The voltage applied must be within power supply specifications of encoder.
Fig. 2-53:
Connection of the resistor
I002806E
Fig. 2-54:
Example of parallel connection with two cables
I002395E
Wiring length
Parallel connection
Larger-size cable
10 m
At least two cables in parallel
Cable gauge 0.2 mm
2
0.4 mm
2
20 m
At least four cables in parallel
0.75 mm
2
100 m
At least six cables in parallel
1.25 mm
2
Tab. 2-35:
Cable gauges and number of parallel cables
PC
RH (OH)
When OH signal is assigned to terminal RH
(Pr.182 = "7")
Resistor (2 W 1 k
Ω
)
2-wire blade terminal
To thermal protector
Insulate
Insulate
PZ2
PZ1
PA1
PA2
FB1
FB2
SD
PG
G
F
D
C
B
A
R
S
PLG
FR-A800
(FR-A8AP)
Example of parallel connection
with two cables
(with complementary encoder output)
2 mm
2
Encoder
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......