Check first when you have a trouble
Protective functions
6 - 38
Parameter
Setting
Start signal operation selection is set by Pr. 250
"Stop selection".
Check the Pr. 250 setting and the connection of
STF and STR signals.
The motor has decelerated to a stop when
power failure deceleration stop function is
selected.
When power is restored, ensure the safety, and
turn OFF the start signal once, then turn ON
again to restart.
When Pr. 261 "Power failure stop selection" = "2
or 12", the motor automatically restarts after
the power is restored.
Performing auto tuning.
When offline auto tuning ends, press STOP/
RESET key of the operation panel for the PU
operation. For the External operation, turn OFF
the start signal (STF or STR).
This operation resets the offline auto tuning,
and the PU's monitor display returns to the
normal indication.
(Without this operation, next operation cannot
be started.)
The automatic restart after instantaneous
power failure function or power failure stop
function has been activated.
(Performing overload operation during input
phase loss may cause voltage insufficiency, and
that may result in detection of power failure.)
Set Pr. 872 "Input phase loss protection
selection" ="1" (input phase failure protection
active).
Disable the automatic restart after
instantaneous power failure function and
power failure stop function.
Reduce the load.
Increase the acceleration time if the function
was activated during acceleration.
The motor test operation is selected under
vector control or PM sensorless vector control.
Check the Pr. 800 "Control method selection"
setting.
When the FR-HC2, FR-CV, or FR-CC2 is used, the
input logic setting of the X10 signal is incorrect.
Set Pr. 599 = "0" (initial value for standard
models and IP55 compatible models) to use the
X10 signal with the NO contact input
specification, and Pr. 599 = "1" (initial value for
separated converter types) to use the X10
signal with the NC contact input specification.
Load
Load is too heavy.
Reduce the load.
⎯
Shaft is locked.
Inspect the machine (motor).
⎯
Check
points
Possible cause
Countermeasure
Refer to
page
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......