(M) Monitor display and monitor output signal
Parameters
5 - 328
Monitor description list (Pr. 52, Pr. 774 to Pr. 776, Pr. 992)
●
Set the monitor to be displayed on the operation panel and parameter unit in Pr. 52, Pr. 774 to Pr.
776, Pr. 992.
●
Refer to the following table and set the monitor to be displayed. (The monitor marked
⎯
cannot
be selected. "
" in the [Minus (-) display] indicates a display with a minus sign.)
1108
M052
Excitation current monitor filter
9999
0 to 5 s
The filter time constant is selectable
for monitoring of the motor
excitation current. A larger setting
results in slower response.
9999
0.3 s filter
Types of
monitor
Unit
Pr. 52,
Pr. 774 to Pr. 776,
Pr. 992
RS-485
communica-
tion dedicat-
ed monitor
(hexadeci-
mal)
MODBUS
RTU real
time
monitor
Minus (-)
display
Description
Output
frequency/
speed
1/0/100
H01
40201
Displays the inverter output
frequency.
Output current
2/0/100
H02
40202
Displays the inverter output
current effective value.
0.1 V
3/0/100
H03
40203
Displays the inverter output
voltage.
Fault display
⎯
0/100
⎯
⎯
Displays 8 past faults
individually.
Frequency
setting value/
speed setting
H05
40205
Displays the set frequency
Running speed
1 (r/min)
H06
40206
Displays the motor speed (by the
Pr. 37, Pr. 144 settings).
(Refer to page 5-324)
The actual motor speed by
encoder signal is used during
encoder feedback control and
vector control.
Motor torque
0.1%
H07
40207
Displays motor torque as a
percentage (0% under V/F
control), considering the rated
torque as 100%.
Converter
output voltage
0.1 V
H08
40208
Displays the DC bus voltage
value.
Regenerative
brake duty
0.1%
H09
40209
Brake duty set in Pr. 30 and Pr. 70
Electronic
thermal O/L
relay load factor
0.1%
H0A
40210
Displays the motor thermal
cumulative value, considering
the thermal operation level as
100%.
Output current
peak value
0.01 A/
0.1 A
H0B
40211
Saves and displays the output
current monitor peak value.
(Cleared with each start.)
Converter
output voltage
peak value
0.1 V
H0C
40212
Saves and displays the DC bus
voltage peak value.
(Cleared with each start.)
Input power
0.01 kW/
0.1 kW
H0D
40213
Displays the power at the
inverter input side.
Output power
0.01 kW/
0.1 kW
H0E
40214
Displays the power at the
inverter output side.
Tab. 5-126:
Monitor description list (1)
Pr.
Name
Initial value
Setting range
Description
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......