5.16.15 Droop
control
This is a function to give droop characteristics to the speed by balancing the load in proportion with
the load torque during the Advanced magnetic flux vector control, Real sensorless vector control, vec-
tor control, and PM sensorless vector control.
This is effective when balancing the load when using multiple inverters.
Pr.
Name
Initial
value
Setting
range
Description
286
G400
Droop gain
0%
0
Normal operation
0.1% to
100%
Droop control enabled
Set the droop amount at the time of rated torque as
% value of the rated motor frequency.
287
G401
Droop filter time constant
0.3 s
0 to 1 s
Set the filter time constant to apply to the current for
torque.
288
G402
Droop function activation
selection
0
0
Without droop control
during acceleration/
deceleration
(With 0 limit)
Rated motor frequency
is the droop
compensation
reference
1
Constantly droop control
during operation
(With 0 limit)
2
Constantly droop control
during operation
(Without 0 limit)
10
Without droop control
during acceleration/
deceleration
(With 0 limit)
Motor speed is the
droop compensation
reference
11
Constantly droop control
during operation
(With 0 limit)
994
G403
Droop break point gain
9999
0.1 to 100%
Set the droop amount to be changed as % value of
the rated motor frequency.
9999
No function
995
G404
Droop break point torque
100%
0.1 to 100%
Set the torque when the droop amount is to be
changed.
679
G420
Second droop gain
9999
0 to 100%
Refer to Pr. 286
Set the second droop
control. The droop
control is enabled when
the RT signal is ON.
9999
The first droop control
setting is applied to the
operation.
680
G421
Second droop filter time
constant
9999
0 to 1 s
Refer to Pr. 287
9999
The first droop control
setting is applied to the
operation.
681
G422
Second droop function
activation selection
9999
0, 1, 2, 10, 11 Refer to Pr. 288
9999
The first droop control
setting is applied to the
operation.
682
G423
Second droop break point
gain
9999
0.1 to 100%
Refer to Pr. 994
9999
The first droop control
setting is applied to the
operation.
683
G424
Second droop break point
torque
9999
0.1 to 100%
Refer to Pr. 995
9999
The first droop control
setting is applied to the
operation.
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Vector
Vector
PM
PM
PM
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......