(A) Application parameters
Parameters
5 - 596
Digital source (monitored item) selection
Select the digital sources (input/output signals) to be set to Pr. 1038 to Pr. 1045 from the table below.
When a value other than the below, 0 (OFF) is applied for display.
Trigger setting (Pr. 1025, Pr. 1035 to Pr. 1037, Pr. 1046, Pr. 1047)
●
Set the trigger generating conditions and trigger target channels.
Setting value
Signal name
Remarks
Setting value
Signal name
Remarks
0
—
—
101
RUN
For the details of the
signals, refer to
page 5-361.
1
STF
For the details of the
signals, refer to
page 5-422.
102
SU
2
STR
103
IPF
3
AU
104
OL
4
RT
105
FU
5
RL
106
ABC
6
RM
107
ABC2
7
RH
121
DO0
For the details of the
signals, refer to the
Instruction Manual of
FR-A8AY (option).
8
JOG
122
DO1
9
MRS
123
DO2
10
STP (STOP)
124
DO3
11
RES
125
DO4
12
CS
126
DO5
21
X0
For the details of the
signals, refer to the
Instruction Manual of
FR-A8AX (option).
127
DO6
22
X1
128
RA1
For the details of the
signals, refer to the
Instruction Manual of
FR-A8AR (option).
23
X2
129
RA2
24
X3
130
RA3
25
X4
26
X5
27
X6
28
X7
29
X8
30
X9
31
X10
32
X11
33
X12
34
X13
35
X14
36
X15
37
DY
Tab. 5-257:
Digital source (monitored item) selection
Pr. 1025
setting
Trigger generating conditions
Selection of trigger
target channel
0
Trace starts when inverter enters an fault status (protective function
activated)
—
1
Trace starts when analog monitor satisfies trigger conditions
Pr. 1035
2
Trace starts when digital monitor satisfies trigger conditions
Pr. 1046
3
Trace starts when either of analog or digital monitor satisfies trigger
conditions (OR)
Pr. 1035, Pr. 1046
4
Trace starts when both of analog or digital monitor satisfies trigger conditions
(AND)
Pr. 1035, Pr. 1046
Tab. 5-258:
Trigger setting
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......