Parameters
Speed control under Real sensorless vector control, vector control, PM sensorless vector control
FR-A800
5 - 95
Trip during torque limit operation (Pr. 874)
●
A trip can be set for when the torque limit is activated and the motor stalls.
●
When a high load is applied and the torque limit is activated under speed control or position
control, the motor stalls. At this time, if a state where the rotation speed is lower than the value
set in Pr. 865 "Low speed detection" and the output torque exceeds the level set in Pr. 874 "OLT
level setting" continues for 3 s, Stall prevention stop (E.OLT) is activated and the inverter output
is shut off.
Adjusting the stall prevention operation signal and output timing (OL signal, Pr. 157)
●
If the output torque exceeds the torque limit level and the torque limit is activated, the stall
prevention operation signal (OL signal) is turned ON for 100 ms or longer. When the output torque
drops to the torque limit level or lower, the output signal also turns OFF.
●
Pr. 157 "OL signal output timer" can be used to set whether to output the OL signal immediately,
or whether to output it after a certain time period has elapsed.
I001508E
Fig. 5-22:
Alarm stop when torque limit is activated
NOTES
Under V/F control or Advanced magnetic flux vector control, if the output frequency drops to
0.5 Hz due to the stall prevention operation and this state continues for 3 s, a fault indication
(E.OLT) appears, and the inverter output is shut off. This operation is activated regardless of the
Pr. 874 setting.
This fault does not occur under the torque control.
Pr. 157 setting
Description
0 (Initial value)
Output immediately.
0.1 to 25
Output after the set time (s).
9999
Not output.
Tab. 5-33:
Setting of parameter 157
Output
frequency [Hz]
Start signal (STF)
Fault signal (ALM)
Pr. 865
Pr. 874
Torque
Output torque
Torque limit
3 s
E.OLT occurrence
Time
Time
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......