(E) Environment setting parameters
Parameters
5 - 222
5.7.18
Inverter parts life display
The degree of deterioration of the control circuit capacitor, main circuit capacitor, cooling fan, and in-
rush current limit circuit can be diagnosed on the monitor.
When a part approaches the end of its life, an alarm can be output by self diagnosis to prevent a fault.
(Note that the life diagnosis of this function should be used as a guideline only, because with the ex-
ception of the main circuit capacitor, the life values are theoretical calculations.)
The setting range (reading only) for separated converter types is "0, 1, 4 or 5". The setting range
(reading only) for IP55 compatible modes is "0 to 31".
The setting is available only for standard models and IP55 compatible models.
Life alarm display and signal output (Y90 signal, Pr. 255)
●
Whether or not the parts of the control circuit capacitor, main circuit capacitor, cooling fan, inrush
current limit circuit, or internal air circulation fans have reached the life alarm output level can be
checked with Pr. 255 "Life alarm status display" and the life alarm signal (Y90). (Internal air
circulation fans are equipped with IP55 compatible models.)
Pr.
Name
Initial
value
Setting
range
Description
255
E700
Life alarm status display
0
(0 to 15)
Displays whether or not the parts of the
control circuit capacitor, main circuit
capacitor, cooling fan, and inrush current
limit circuit have reached the life alarm
output level. Read-only.
256
E701
Inrush current limit circuit life
display
100%
(0 to 100%)
Displays the deterioration degree of the
inrush current limit circuit. Read-only.
257
E702
Control circuit capacitor life
display
100%
(0 to 100%)
Displays the deterioration degree of the
control circuit capacitor. Read-only.
258
E703
Main circuit capacitor life display
100%
(0 to 100%)
Displays the deterioration degree of the
main circuit capacitor. Read-only.
The value measured by Pr. 259 is displayed.
259
E704
Main circuit capacitor life
measuring
0
0, 1
(2, 3, 8, 9)
Setting "1" and turning the power supply
OFF starts the measurement of the main
circuit capacitor life.
If the setting value of Pr. 259 becomes "3"
after turning the power supply ON again, it
means that the measurement is completed.
The deterioration degree is read to Pr. 258.
NOTE
In the life diagnosis of the main circuit capacitor, the alarm signal (Y90) is not output unless meas-
urement by turning OFF the power supply is performed.
I002550E
Fig. 5-78:
Bits of parameter 255
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
7
0
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
(Standard models and IP55 compatible models only)
bit2 Cooling fan life
bit3 Inrush current limit circuit life
(Standard models and IP55 compatible models only)
bit 15
• Pr. 255 read
• Pr. 255 setting read
Bit image is displayed
in decimal
bit4 Life of internal air circulation fans (IP55 compatible models only)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......