Parameters
(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
FR-A800
5 - 251
5.8.4 Starting
frequency
and
start-time hold function
It is possible to set the starting frequency and hold the set starting frequency for a certain period of
time.
Set these functions when a starting torque is needed or the motor drive at start needs smoothing.
Starting frequency setting (Pr. 13)
●
The frequency at start can be set in the range of 0 to 60 Hz.
●
Set the starting frequency at which the start signal is turned ON.
Start-time hold function (Pr. 571)
●
This function holds during the period set in Pr. 571 and the output frequency set in Pr. 13 "Starting
frequency".
●
This function performs initial excitation to smooth the motor drive at a start.
Pr.
Name
Initial value
Setting range
Description
13
F102
Starting frequency
0.5 Hz
0 to 60 Hz
Set the starting frequency at which
the start signal is turned ON.
571
F103
Holding time at a start
9999
0 to 10 s
Set the holding time of Pr. 13.
9999
The holding function at a start is
invalid.
Fig. 5-102:
Starting frequency parameter
I002566E
NOTE
The inverter does not start if the frequency setting signal is less than the value set in Pr. 13.
For example, while Pr. 13 = 5 Hz, the inverter output starts when the frequency setting signal
reaches 5 Hz.
Fig. 5-103:
Holding time at start
I002567E
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Vector
Vector
60
0
Output
frequency
(Hz)
Time
ON
STF
Pr. 13
Setting r
a
nge
0
60
Output
frequency
(Hz)
Setti
n
g
rang
e
Pr. 13
STF
Pr. 571 setting time
Time
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......