(E) Environment setting parameters
Parameters
5 - 190
5.7.1
Real time clock function
The time can be set. The time can only be updated while the inverter power is ON.
The real time clock function is enabled using an optional LCD operation panel (FR-LU08).
Simple clock function
When the year, month, day, time and minute are set in the parameters, the inverter counts the date
and time. The date and time can be checked by reading the parameters.
Pr.
Name
Initial
value
Setting range
Description
1006
E020
Clock (year)
2000
2000 to 2099
Set the year.
1007
E021
Clock (month, day)
101
(January
1)
101 to 131, 201 to 228,
(229), 301 to 331,
401 to 430, 501 to 531,
601 to 630, 701 to 731,
801 to 831, 901 to 930,
1001 to 1031, 1101 to 1130,
1201 to 1231
Set the month and day.
1000 and 100 digits: January to December
10 and 1 digits: 1 to end of month (28, 29, 30
or 31)
For December 31, set "1231".
1008
E022
Clock (hour, minute)
0
(00:00)
0 to 59, 100 to 159,
200 to 259, 300 to 359,
400 to 459, 500 to 559,
600 to 659, 700 to 759,
800 to 859, 900 to 959,
1000 to 1059, 1100 to 1159,
1200 to 1259, 1300 to 1359,
1400 to 1459, 1500 to 1559,
1600 to 1659, 1700 to 1759,
1800 to 1859, 1900 to 1959,
2000 to 2059, 2100 to 2159,
2200 to 2259, 2300 to 2359
Set the hour and minute using the 24-hour
clock.
1000 and 100 digits: 0 to 23 hours
10 and 1 digits: 0 to 59 minutes
For 23:59, set "2359".
NOTES
The clock's count-up data is saved in the inverter's EEPROM every 10 minutes.
Because the date and time are cleared after turning OFF the control circuit power supply, the clock
function must be reset after turning ON the power supply. Use a separate power supply, such as
an external 24 V power supply, for the control circuit of the simple clock function, and supply
power continuously to this control circuit.
In the initial setting, inverter reset is performed if supplying power to the main circuit is started
when power is supplied only to the control circuit. Then, the clock information stored in EEPROM
is restored. Reset at the start of supplying power to the main circuit can be disabled by setting Pr.
30 "Regenerative function selection". (Refer to page 5-675.)
The set clock is also used for functions such as faults history.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......