(N) Operation via communication and its settings
Parameters
5 - 646
Output signal LF "alarm output (communication error warning)"
During a communication error, the alarm signal (LF signal) is output by open collector output. Assign
the terminal to be used using any of Pr. 190 to Pr. 196 (output terminal function selection).
Signal loss detection (Pr. 539 "MODBUS RTU communication check time interval")
●
If a signal loss (communication) is detected between the inverter and the master as a result of a
signal loss detection, an inverter communication fault (E.SER) occurs and the inverter trips.
●
When the setting is "9999", communication check (signal loss detection) is not made.
●
When the setting is "0", reading, etc. of monitors and parameters is possible, though a Communi-
cation fault (inverter) (E.SER) occurs instantly when the Network operation mode is switched to.
●
A signal loss detection is made when the setting is any of "0.1 s to 999.8 s". To make a signal loss
detection, it is necessary to send data from the master within the communication check time
interval. (The inverter makes a communication check (clearing of communication check counter)
regardless of the station number setting of the data sent from the master).
●
The communication check is made from the first communication in the Network operation mode
(can be changed by Pr. 551 "PU mode operation command source selection").
●
The communication check time by query communication includes a no data time (3.5 bytes).
This no data time differs according to the communication speed, so take this time no data time
into consideration when setting the communication check time.
I001229E
Fig. 5-318:
Output of the LF signal
NOTE
The LF signal can be assigned to an output terminal by setting Pr. 190 to Pr. 196. Changing the ter-
minal assignment may affect other functions. Set parameters after confirming the function of each
terminal.
Master
Slave
Communication
error count
(Pr. 343)
Signal LF
Alarm data
Alarm data
Normal data
Reply data
Normal data
Alarm data
Reply data
OFF
OFF
OFF
ON
ON
Communication error count is increased in
synchronization with leading edge of LF signal
Turns off when normal data is received
Alarm data:
Data resulting in communication error.
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......