Parameters
Speed control under Real sensorless vector control, vector control, PM sensorless vector control
FR-A800
5 - 93
Changing the setting increments of the torque limit level (Pr. 811)
●
The setting increments of Pr. 22 "Torque limit level" and Pr. 812 to Pr. 817 (torque limit level) can
be changed to 0.01% by setting Pr. 811 "Set resolution switchover" = "10, 11".
For the change of the speed setting increments using a communication option, refer to the
Instruction Manual of the communication option.
Changing the torque characteristic of the constant-output range (Pr. 803)
In torque limit operations under Real sensorless vector control or vector control, the torque charac-
teristic in a low-speed range and constant-output range can be changed.
Valid only under Real sensorless vector control.
Pr. 811 setting
Speed setting, running speed monitor increments from PU,
RS-485 communication, communication options
Torque limit setting increments
Pr. 22, Pr. 812 to Pr. 817
0
1 r/min
0.1%
1
0.1 r/min
10
1 r/min
0.01%
11
0.1 r/min
Tab. 5-31:
Torque limit level increments
NOTES
The internal resolution of the torque limit is 0.024% (100/2
12
), and fractions below this resolution
are rounded off.
When Real sensorless vector control is selected, fractions below a resolution equivalent to 0.1%
are rounded off even if Pr. 811 = "10, 11" is set.
For details on changing the speed setting increments, refer to page 5-324.
Pr. 803 setting
Torque characteristic in low-speed range
Torque characteristic in constant-output
range
0
Torque rise
Constant motor output
1
Constant torque
Constant torque
10
Constant torque
Constant motor output
11
Torque rise
Constant torque
Tab. 5-32:
Torque characteristic in a low-speed range and constant-output range
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......