Parameters
(N) Operation via communication and its settings
FR-A800
5 - 609
NOTES
Fault output indicates the Fault signal (ALM) and an alarm bit output.
When the fault output is set enabled, fault records are stored in the faults history. (A fault record is
written to the faults history at a fault output.)
When the fault output is not set enabled, fault record is overwritten to the faults history of the
faults history temporarily but not stored.
After the fault is removed, the fault indication goes back to normal indication on the monitor, and
the faults history goes back to the previous status.
If Pr. 502 is set to "1, 2, or 3", the normal deceleration time setting (settings like Pr. 8, Pr. 44, and
Pr. 45) is applied as the deceleration time. Normal acceleration time setting (settings like Pr. 7 and
Pr. 44) is applied as the acceleration time for restart.
When Pr. 502 = "2 or 3", the inverter operates with the start command and the speed command,
which were used before the fault.
If a communication line error occurs, then the error is removed during deceleration while Pr. 502 =
"2", the motor re-accelerates from that point.
The Pr. 502 and Pr. 779 settings are valid when communication is performed via the RS-485 termi-
nals or a communication option.
These parameters are valid under the Network operation mode. When performing communica-
tion with RS-485 terminals, set Pr. 551 "PU mode operation command source selection" to "2 (ini-
tial value)".
Pr. 502 is valid for the device that has the command source under the Network operation mode. If
a communication option is installed while Pr. 550 = "9999 (initial value)", a communication error in
RS-485 terminals occurs and Pr. 502 becomes invalid.
If the communication error setting is disabled with Pr. 502 = "3", Pr. 335 = "9999", and Pr. 539 =
"9999", the inverter does not continue its operation with the frequency set by Pr. 779 at a commu-
nication error.
If a communication error occurs while continuous operation at Pr. 779 is selected with Pr. 502 =
"3", the inverter operates at the frequency set in Pr. 779 even though the speed command source
is at the external terminals.
Example) If a communication error occurs while Pr. 339 = "2" and the external terminal RL is ON,
the operation is continued at the frequency set in Pr. 779.
During position control, a fault is output without deceleration even if Pr. 502 = "2".
Parameters referred to
Pr. 7
Acceleration time
=>
Pr. 8
Deceleration time
=>
Pr. 335
RS-485 communication retry count
=>
Pr. 336
RS-485 communication check time interval
=>
Pr. 539
MODBUS RTU communication check time interval
=>
Pr. 550
NET mode operation command source selection
=>
Pr. 551
PU mode operation command source selection
=>
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......