(C) Motor constant parameters
Parameters
5 - 450
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Changing the motor constant (if setting motor constants in the internal data of the inverter)
●
Set Pr. 71 as follows.
First
motor Pr.
Second
motor Pr.
Name
Setting range
Setting
increments
Initial value
82
455
Motor excitation current
(No-load current)
0 to 500 A, 9999
0.01 A
9999
0 to 3600 A, 9999
0.1 A
90
458
Motor constant (R1)
0 to 50 Ω, 9999
0.001 Ω
0 to 400 mΩ, 9999
0.01 mΩ
91
459
Motor constant (R2)
0 to 50 Ω, 9999
0.001 Ω
0 to 400 mΩ, 9999
0.01 mΩ
92
460
Motor constant (L1)/d-shaft
inductance (Ld)
0 to 6000 mH, 9999
0.1 mH
0 to 400 mH, 9999
0.01 mH
93
461
Motor constant (L2)/q-shaft
inductance (Lq)
0 to 6000 mH, 9999
0.1 mH
0 to 400 mH, 9999
0.01 mH
94
462
Motor constant (X)
0 to 100%, 9999
0.1%
0.01%
859
860
Torque current/Rated PM motor
current
0 to 500 A, 9999
0.01A
0 to 3600 A, 9999
0.1 A
298
560
Frequency search gain
0 to 32767, 9999
1
Tab. 5-181:
Parameter setting ranges
NOTE
If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi motors (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA and SF-V5RU (1500 r/min series) and so on) are used.
Motor
Pr. 71 setting
Mitsubishi standard motor
Mitsubishi high-efficiency motor
SF-JR and SF-TH
3 (4)
SF-JR 4P 1.5 kW or lower
23 (24)
SF-HR
43 (44)
Others
3 (4)
Mitsubishi constant-torque motor
SF-JRCA 4P
SF-TH (constant-torque)
13 (14)
SF-HRCA
53 (54)
Other (SF-JRC, etc.)
13 (14)
Mitsubishi high-performance energy-
saving motor
SF-PR
73 (74)
Vector control dedicated motor
SF-V5RU (1500 r/min series)
SF-THY
33 (34)
SF-V5RU (other than the 1500 r/min series)
13 (14)
Other manufacturer's standard motor
⎯
3 (4)
Other manufacturer's constant-torque
motor
⎯
13 (14)
Tab. 5-182:
Motor selection
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......