(G) Control parameters
Parameters
5 - 656
5.16.3
Load pattern selection
Optimal output characteristics (V/F characteristics) for application or load characteristics can be se-
lected.
Application for constant-torque load (Pr. 14 = "0", initial value)
●
The output voltage will change linearly against the output frequency at the base frequency or
lower. (1.75th-power curve for FR-A820-01870(37K) or higher, and FR-A840-00930(37K) or higher)
●
Set this parameter when driving a load that has constant load torque even when the rotation
speed is changed, such as conveyor, dolly, or roll drive.
Parameters referred to
Pr. 14
Load pattern selection
=>
Pr. 29
Acceleration/deceleration pattern selection
=>
Pr. 71
Applied motor
=>
Pr. 83
Rated motor voltage
=>
Pr. 84
Rated motor frequency
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>
Pr.
Name
Initial
value
Setting
range
Description
14
G003
Load pattern selection
0
0
For constant-torque load
1
For variable-torque load
2
For constant-torque lift
(boost at reverse rotation 0%)
3
For constant-torque lift
(boost at forward rotation 0%)
4
RT signal ON.................for constant-torque load
RT signal OFF ...............for constant-torque lift, boost at
reverse rotation 0%
5
RT signal ON.................for constant-torque load
RT signal OFF ...............for constant-torque lift, boost at
forward rotation 0%
Fig. 5-324:
Constant-torque load
I002750E
NOTE
Select for constant-torque load (setting value "0") even for fan and pump in following cases.
●
When accelerating a blower with large moment of inertia (J) in a short period of time.
●
When it is a constant-torque load such as rotary pump or gear pump.
●
When the load torque increases in low speed such as screw pump.
V/F
V/F
V/F
100%
Ou
tp
u
t v
o
lt
ag
e
Pr. 3 Base frequency
Output frequency (Hz)
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......