Parameters
(T) Multi-Function Input Terminal Parameters
FR-A800
5 - 433
Start signal selection
NOTES
The STP (STOP) signal is assigned to the STP (STOP) terminal by the initial setting. Set "25" in any of
Pr. 178 to Pr. 189 to assign the STP (STOP) signal to another terminal.
When the JOG operation is enabled by turning ON the JOG signal, STP (STOP) signal will be disa-
bled.
Even when the output is stopped by turning ON the MRS signal, self-holding function is not can-
celled.
STF
STR
Pr. 250 setting and inverter condition
0 to 100 s, 9999
1000 s to 1100 s, 8888
OFF
OFF
Stop
Stop
OFF
ON
Reverse rotation
ON
OFF
Forward rotation
Forward rotation
ON
ON
Stop
Reverse rotation
Tab. 5-170:
Start signal selection
Parameters referred to
Pr. 4 to Pr. 6
(multi-speed setting)
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......