(M) Monitor display and monitor output signal
Parameters
5 - 350
Calibration procedure for terminal FM when using the operation panel (FR-DU08)
NOTES
When outputting such an item as the output current, which cannot reach a 100% value easily by
operation, set Pr. 54 to "21" (reference voltage output) and calibrate. 1440 pulses/s are output
from the terminal FM.
When Pr. 310 "Analog meter voltage output selection" = "21", the terminal FM calibration cannot
be performed. For the details of Pr. 310, refer to the Instruction Manual of FR-A8AY.
The wiring length of the terminal FM should be 200 m at maximum.
The initial value of the calibration parameter C0 (Pr. 900) is set to 1 mA full-scale and 1440 pulses/s
terminal FM pulse train output at 60 Hz. The maximum pulse train output of terminal FM is 2400
pulses/s.
When connecting a frequency meter between terminals FM-SD and monitoring the running fre-
quency, it is necessary to change Pr. 55 to the maximum frequency, since the FM terminal output
will be saturated at the initial value when the maximum frequency reaches 100 Hz or greater.
Calibration with the calibration parameter C0 (Pr. 900) cannot be done when Pr. 291 "Pulse train I/O
selection" = "10, 11, 20, 21, 100" (high-speed pulse train output).
Operation
Screen at power-ON
The monitor display appears.
Changing the operation mode
Press
to choose the PU operation mode. [PU] indicator is lit.
Calibration is also possible in the External operation mode.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
#
Calibration parameter selection
Turn
until
appears. Press
to display
.
,
Selecting the parameter number
Turn
until
(C0 (Pr. 900) FM/CA terminal calibration) appears. Press
to enable the parameter
setting. The monitored value of the item (initially the output frequency) selected by Pr. 54 FM/CA terminal function
selection will appear.
$
Pulse output via terminal FM
If stopped, press
or
to start the inverter operation. (To monitor the output frequency, motor
connection is not required.
When a monitor that does not require inverter operation is set in Pr. 54, calibration is also possible during a stop status.
%
Scale adjustment
Turn
to move the meter needle to a desired position.
&
Setting completed
Press
to enter the setting. The monitored value and
flicker alternately.
앫
Turn
to read another parameter.
앫
Press
to return to the
display.
앫
Press
twice to show the next parameter.
Tab. 5-137:
FM terminal calibration
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......