Parameters
(M) Monitor display and monitor output signal
FR-A800
5 - 379
5.11.9 Output
torque
detection
A signal is output when the motor torque is higher than the setting. This function can be used for elec-
tromagnetic brake operation, open signal, etc.
●
The Torque detection (TU) signal turns ON when the output torque reaches the detection torque
value set in Pr. 864 or higher. The TU signal turns OFF when the output torque drops lower than
the detection torque value.
●
Pr. 864 is not available under V/F control.
●
For the TU signal, set "35 (positive logic) or 135 (negative logic)" in one of Pr. 190 to Pr. 196 (output
terminal function selection) to assign the function to the output terminal.
E
CAUTION:
●
The zero current detection level setting should not be too low, and the zero current detection
time setting not too long. When the output current is low and torque is not generated, the
detection signal may not be output.
●
Even when using the zero current detection signal, a safety backup such as an emergency
brake must be provided to prevent hazardous machine or equipment conditions.
Parameters referred to
Online auto tuning
=>
Offline auto tuning
=>
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Pr.
Name
Initial value
Setting range
Description
864
M470
Torque detection
150%
0 to 400%
Set the torque value where the TU
signal turns ON.
Fig. 5-177:
Torque detection
I002630E
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Vector
Vector
PM
PM
PM
TU
Time
Pr. 864
Output t
o
rq
ue
(%
)
ON
OFF
Summary of Contents for FR-A800
Page 2: ......
Page 4: ......
Page 22: ...Contents XVIII ...
Page 30: ...Related manuals Introduction 1 8 ...
Page 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Page 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 934: ...Check first when you have a trouble Protective functions 6 46 ...
Page 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Page 1032: ...EC Declarations of Conformity Appendix A 48 ...
Page 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1034: ...EC Declarations of Conformity Appendix A 50 ...
Page 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Page 1036: ...EC Declarations of Conformity Appendix A 52 ...
Page 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1038: ...EC Declarations of Conformity Appendix A 54 ...
Page 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1040: ...EC Declarations of Conformity Appendix A 56 ...
Page 1041: ......